System Sensor Computer Drive B501BHT User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS  
3825 Ohio Avenue, St. Charles, Illinois 60174  
1-800-SENSOR2, FAX: 630-377-6495  
B501BHT  
Temporal Tone Sounder Base  
Specifications  
Base Diameter:  
6.0 inches (15.2 cm)  
Base Height (less sensor):  
Weight:  
2.3 inches (5.9 cm)  
0.4 lb. (181 gm)  
Operating Temperature Range:  
Operating Humidity Range:  
Electrical Ratings  
32° to 120°F (0° to 49°C)  
10% to 93% Relative Humidity  
External Supply Voltage:  
17 to 32 VDC  
Standby Current:  
Alarm Current:  
1.0 mA maximum  
15 mA maximum  
10% of supply voltage  
200 µF  
Maximum Ripple Voltage:  
Start-up Capacitance:  
Communication/Initiating Loop Supply  
Current Draw from Remote Output  
of Sensor to turn on Horn:  
Sound Output:  
700 µA maximum  
Greater than 90 dBA measured in anechoic room at 10 feet, 24 volts. 85 dBA minimum  
measured in UL reverberant room.  
Before Installing  
NOTE: When not used as a supplementary evacuation system  
the external 24 VDC supply shall be treated as a component of  
the main power supply system and shall fall under the require-  
ments of the main power supply system per NFPA 72.  
Please read the System Smoke Detector Application Guide,  
which provides detailed information on sensor spacing. place-  
ment, zoning, wiring, and special applications. Copies of this  
manual are available from System Sensor. NFPA 72 and NEMA  
guidelines should be observed.  
B501BHT Terminals  
No.  
Function  
NOTICE: This manual should be left with the owner/user of  
this equipment.  
1
2
3
4
5
External Supply Positive (+)  
External Supply Negative (–)  
Negative (–) Comm. Line In and Out  
Positive (+) Comm. Line In and Out  
Sounder Base Interconnect  
IMPORTANT: The detector used with this base must be tested  
and maintained regularly following NFPA 72 requirements.  
The detector should be cleaned at least once a year.  
General Description  
Terminals 3 and 4 are used for the communication circuit.  
The B501BHT sounder base is used with System Sensor 200  
and 500 Series sensor heads. Refer to the appropriate manual  
for more information on sensors.  
Mounting  
Mount the B501BHT directly to an electrical box, using the  
mounting kit, supplied (see Figure 2).  
The B501BHT incorporates the distinctive three-pulse tempo-  
ral pattern fire alarm evacuation signal now required by NFPA  
72 for commercial and residential applications.  
The sounder base is 1.1-inches deep. Electrical boxes must  
1
be 4-inches square by at least 1 ⁄2 inches deep - 218 inches is  
recommended.  
The sounder base is intended for use with intelligent systems.  
Refer to the panel manual for the maximum allowable num-  
ber of units per loop. The sounder base requires an external  
24VDC supply with reverse polarity capability or a relay mod-  
ule configured to reverse the power as in Figure 5. The con-  
nections for the external supply (terminals 1 and 2) and the  
communication loop (terminals 3 and 4) are isolated to pre-  
vent electrical interaction between them.  
NOTE: A maximum space of 18 inch from the outside edge of  
the electrical box to the inside edge of the drywall or ceiling  
tile is allowable.  
Wiring Guidelines  
All wiring must be installed in compliance with the National  
Electrical Code and the local codes having jurisdiction and  
must not be of such length or wire size which would cause  
the base to operate outside of its published specifications. The  
conductors used to connect smoke sensors to control panels  
and accessory devices should be color coded to reduce the  
likelihood of wiring errors. Improper connections can prevent  
a system from responding properly in the event of a fire.  
When the sensor’s visible LEDs are latched on for approxi-  
mately 10 seconds, the associated horn sounds. A loop of  
horns can be made to sound by reversing the polarity of the  
external supply when configured as in Figure 4 and 5. When  
configured as in Figure 5, a loop of horns can also be made to  
sound by turning on the Intelligent Relay Module.  
D550-06-00  
1
I56-1367-004R  
 
Figure 4. Wiring diagram:  
Detector Activates Sounder Base(s) - (Complies with UL268)  
gether using terminal 5, Sounder Base Interconnect, as shown  
in the diagram.  
UL has approved grouping for up to six B501BHT base with  
horn units. When wired as a group, any detector in the group  
that has its LED’s latched on by the panel will cause other  
B501BHT units in the group to sound. This type of “local”  
grouping is accomplished by wiring the grouped devices to-  
NOTE: Since a local grouping of horns is not supervised, the  
groups can only be used as a supplementary evacuation system.  
It is not acceptable to group horns for primary alarm signaling.  
CLASS A OPTIONAL WIRING  
INTELLIGENT  
MONITOR  
MODULE  
OPTIONAL SOUNDER INTERCONNECT  
*
(+)  
(–)  
2
1
(+) COMM.  
6
7
4
5
4
5
4
5
U.L.  
LISTED  
EOL  
3
2 1  
3
2 1  
3
2 1  
RESISTOR  
47K  
(–) COMM.  
U.L.  
LISTED  
EOL  
RELAY  
24V  
(–) POWER  
(+) POWER  
CLASS A OPTIONAL WIRING  
C0474-00  
GROUPING OF UP TO 6 MODEL B501BHT TEMPORAL TONE SOUNDER BASES.  
*
Figure 5. Wiring diagram:  
Detector Activates Sounder Base(s); Intelligent Relay Module Ac- gether using terminal 5, Sounder Base Interconnect, as shown  
tivates All Sounder Bases - (Complies with UL 268 and UL 464) in the diagram.  
grouping is accomplished by wiring the grouped devices to-  
UL has approved grouping of up to six B501BHT bases with NOTE: Since a local grouping of horns is not supervised, the  
horn units. When wired as a group, any detector in the group groups can only be used as a supplementary evacuation sys-  
that has its LED’s latched on by the panel will cause other tem. It is not acceptable to group horns for primary alarm  
B501BHT units in the group to sound. This type of “local” signaling.  
INTELLIGENT  
MONITOR  
OPTIONAL SOUNDER INTERCONNECT  
*
MODULE  
UL LISTED  
INTELLIGENT  
RELAY  
COMPATIBLE  
CONTROL  
PANEL  
(+)  
(–)  
FIRST  
SOUNDER  
BASE  
LAST  
SOUNDER  
BASE  
MODULE  
(+) COMM.  
(–) COMM.  
UL LISTED  
EOL  
SLC  
RESISTOR  
47k  
UL  
LISTED  
EOL  
RELAY  
24V  
(–) POWER  
(+) POWER  
UL LISTED  
24V SUPPLY  
THIS IS A STANDARD RELAY  
MODULE CONFIGURED TO  
REVERSE THE POWER  
C0968-00  
GROUPING OF UP TO 6 MODEL B501BHT TEMPORAL TONE SOUNDER BASES.  
*
D550-06-00  
3
I56-1367-004R  
 
Please refer to insert for the Limitations of Fire Alarm Systems  
THREE-YEAR LIMITED WARRANTY  
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a  
System Sensor warrants its enclosed smoke detector base to be free from defects in mate-  
rials and workmanship under normal use and service for a period of three years from date  
of manufacture. System Sensor makes no other express warranty for this smoke detector  
base. No agent, representative, dealer, or employee of the Company has the authority to  
increase or alter the obligations or limitations of this Warranty. The Company’s obligation  
of this Warranty shall be limited to the repair or replacement of any part of the smoke  
detector base which is found to be defective in materials or workmanship under normal  
use and service during the three year period commencing with the date of manufacture.  
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return  
Authorization number, send defective units postage prepaid to: System Sensor, Returns  
note describing the malfunction and suspected cause of failure. The Company shall not  
be obligated to repair or replace units which are found to be defective because of damage,  
unreasonable use, modifications, or alterations occurring after the date of manufacture.  
In no case shall the Company be liable for any consequential or incidental damages for  
breach of this or any other Warranty, expressed or implied whatsoever, even if the loss  
or damage is caused by the Company’s negligence or fault. Some states do not allow the  
exclusion or limitation of incidental or consequential damages, so the above limitation  
or exclusion may not apply to you. This Warranty gives you specific legal rights, and you  
may also have other rights which vary from state to state.  
D550-06-00  
4
I56-1367-004R  
©2007 System Sensor  
 

Shark Vacuum Cleaner V1310 User Manual
SIIG Computer Drive 104 0561C User Manual
Silicon Image Network Card 5800BU 00DSR User Manual
Snapper Patio Furniture NP216012 User Manual
Sony Laptop VPCF120FDB User Manual
Sony Portable DVD Player D V55 User Manual
Sony Printer DPP EX50 User Manual
Sony Projection Television KP 46WT500 User Manual
Sunbeam Blood Pressure Monitor 7682 User Manual
Suunto Watch X6HR User Manual