SMD-401M
Smoke Dampers
Extruded Airfoil Blades
UL 555S Leakage Class I
APPLICATION
Model SMD-401M is a class I leakage rated modulating smoke
damper. The model SMD-401M serves the function of
both a control damper and smoke damper. High strength airfoil
blades ensure the lowest resistance to airflow in HVAC systems
with velocities to 2000 fpm (10.2 m/s ) and 4 wg (1 kPa). Model
SMD-401M may be installed vertically (with blades running
horizontal) or horizontally and is rated for airflow and leakage in
either direction.
Model SMD-401M meets the requirements for smoke
dampers established by:
National Fire Protection Association
NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
ICBO Uniform Building Codes
New York City (MEA listing #260-91-M)
CSFM California State Fire Marshal
Leakage (Smoke) Damper Listing (#3230-0981:108)
RATINgS
Leakage Class:
I
Operational Rating: Actual ratings are size dependent.
Max. Velocity:
Max. Pressure:
Temperature:
up to 2000 fpm (10.2 m/s)
4 in. wg (1 kPa)
250°F (121ºC) with all actuators.
“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555S (Listing #R13317)
STANDARD CONSTRUCTION
Frame:
5 in. x 1 in. (127mm x 25mm)
galvanized steel hat channel with
reinforced corners. A low profile
head and sill are used on sizes
less than 17 in. (432mm) high to
maximize free area and
performance.
Blades:
Seals:
Airfoil shape constructed of
heavy gauge extruded aluminum.
Structural reinforcement through
the entire length.
Extruded silicone rubber blade
seals. Flexible stainless steel
jamb seals.
LH
Linkage:
Axles:
Bearings:
Concealed in jamb.
1⁄2 in. (13mm) dia. plated steel.
Bronze sleeve type.
SIzE LIMITATIONS:
H*
Minimum Size:
8 in. W x 8 in. H
(203mm W x 203mm H)
RH
Maximum Size:
Single Section:
36 in. W x 36 in.H
(914mm W x 914mm H)
W*
Multi Section:
144 in. W x 36 in. H
(3658mm W x 914mm H)
Optional Features:
• Galvanized steel sleeves.
• Stainless steel bearings
*W&H dimensions furnished approximately 1/4 in. (6mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
• OCI (Open closed indication switches)
• Electric or pneumatic actuators to accomplish smoke
management and system functions.
• POC Retaining angles
• Smoke detector
• Momentary switch
• Transitions (R, C, O)
• Sealed transitions and sleeves
Application Data
Damper Sideplate and Sleeve Dimensional Data
The drawings below illustrate the factory standard sideplate and sleeve mountings for the SMD-401M. The standard "A"
dimensions listed in the table provide adequate space for the mounting of actuators and controls.
If space constraints are a problem the "A" dimension can be varied between 5 3⁄8 in. (136mm) and 12 in. (305mm).
Sideplate
1
1
/2" max.
Sleeve
"A" Dimension
in. (mm)
Sleeve
Standard
Sideplate
Maximum
12 (305)
33/4
"
All Dampers*
7 3/16 (183)
6 3/16 (157)
When height is
11 in. (279) or
less with OCI
11 3/16
(284)
12
(305)
10 3/16
(259)
6 in.
*With the exception of dampers 11 in. (279mm) high or less (12 in.
(305mm)high or less if width is greater than 64 in. (1625mm)) with OCI
option.
Varies
53/8
"
** On dampers 11 in. (279mm) high or less (12 in. (305mm)high or less if
width is greater than 64 in. (1625mm)) with OCI option, sideplate is 16 in.
(406mm)
A
5"
Sleeve Length
5 in.
12 in.**
A
T*
Space Envelopes Required for
S
Actuators and Accessories
Externally mounted actuators always require space
outside of the damper sideplate or sleeve. The “S”
dimension illustrates the clearance required for various
available actuators.
On dampers less than 18 in. (457mm) high, actuators
may also require clearances above and/or below the
sideplate or sleeve. “B” and “T” dimensions are worst
case clearance requirements for some dampers less
than 18 in. (457mm) high. All damper sizes under 18
in. (457mm) high do not require these worst case
clearances. If space availability above or below the
damper sleeve is limited, each damper size should be
individually evaluated.
B*
B*
With OCI
T*
Actuator Type/Model
S
With OCI
Pneumatic
2 1/2 in. (64mm) 5 1/4 in. (133mm)
331-2976
6 in. (152m)
* For dampers 18 in.(457mm) or more in height these dimensions are 0 in.
1
Note: This actuator requires field calibration for the zero and span setting.
Transitioned Damper Dimensions
When a fire/smoke damper is being used in conjunction with round or oval ductwork, the SMD-401M can be supplied in a
factory sleeve with round or oval transitions on both ends of the sleeve. Dampers should be ordered to the duct dimensions.
Drawings below show overall damper size.
D*+
2 in. (51mm) +T
s
W*+ 2 in. (51mm)+T
s
W*+ 2 in. (51mm)+T
s
D*+ 2 in. (51mm)+T
s
H*+ 2 in. (51mm)+T
H*+ 2 in. (51mm)+T
s
s
H*
H*
21/8in.
21/8in.
(54mm)
21/8in.
(54mm)
(54mm)
*
W
W*
D*
16 in. (406mm)
Min.
16 in. (406mm)
Min.
16 in. (406mm)
Min.
TYPE R
TYPE O
TYPE C
These dimensions are furnished approximately 1/4 in. (6mm) undersize, except round and oval dimensions which are
*
approximately 1/8 in. (3mm) undersize.
T = (2)(Sleeve Thickness)
s
Specifications
Smoke Dampers meeting the following specifications
shall be furnished and installed where shown on plans
and/or as described in schedules. Dampers shall meet
the requirements of NFPA 90A, 92A, 92B, 101 and 105 and
further shall be tested, rated and labeled in accordance with
the latest edition of UL Standard 555S. Smoke dampers
shall be of low leakage design qualified to UL 555S Leakage
Class I.
Damper blades shall be hollow extruded aluminum airfoil
type with structural reinforcing tube running full length of
each blade. Damper frame shall be galvanized steel formed
into a structural hat channel shape with reinforced corners.
Bearings shall be sintered bronze sleeve type rotating in
extruded holes in the damper frame. Blade edge seals
shall be silicone rubber designed to inflate and provide a
tighter seal against leakage as pressure on either side of
the damper increases. Jamb seals shall be stainless steel
compression type. Damper must be rated for mounting
vertically (with blades running horizontal) or horizontally and
be UL 555S rated for leakage and airflow in either direction
through the damper.
Each damper/actuator combination shall have a UL555S
elevated temperature rating of 250°F (121ºC) minimum and
shall be rated to operate at maximum design airflow at its
installed location. Each damper shall be supplied with an
appropriate actuator installed by the damper manufacturer
at the time of damper fabrication. Damper actuator shall be
(specifier select one of the following) electric type for 24 volt
operation.
The basis of design is Greenheck Model SMD-401M.
Copyright © 2007 Greenheck Fan Corporation