HP Hewlett Packard Power Supply R5500 User Manual

Overview  
The ERM consists of two battery packs in a 3U chassis. The  
ERM connects directly to a UPS R5500 or to another ERM. Up  
to two ERM units can be connected.  
HP UPS R5500 ERM  
Installation Instructions  
At the HP recommended 80 percent load, one ERM extends  
the available UPS runtime up to 30 minutes.  
For more information about any of the topics covered in this  
document, see the UPS user guide located on the  
documentation CD or HP website  
Precautions  
WARNING: A risk of personal injury from  
electric shock and hazardous energy levels  
exists. The installation of options and routine  
maintenance and service of this product  
must be performed by individuals who are  
knowledgeable about the procedures,  
precautions, and hazards associated with AC  
power products.  
This symbol indicates that the ERM  
exceeds the recommended weight for  
one individual to handle safely.  
75 kg  
WARNING: To reduce the risk of  
167 lb  
personal injury or damage to the  
equipment, observe local occupational  
health and safety requirements and  
guidelines for manual material  
handling.  
CAUTION: Always plan the rack installation so that  
the heaviest item is on the bottom of the rack. Install  
the heaviest item first, and continue to populate the  
rack from the bottom to the top.  
ERM kit contents  
Important Safety Information guide  
This document  
Warranty information  
Rails, with mounting hardware for square- and  
round-holed racks  
ERM  
Front bezel  
Rear mounting brackets, plates, and  
associated hardware  
June 2006 (Third Edition)  
Part Number 351641-003  
 
 
2. Insert screws through the rack into the mounting rail and  
5. Tighten the hex nuts.  
the front of each mounting bracket.  
3. Install cage nuts or clip nuts into the rear of the rack.  
Preparing the rails for  
integrated shipping  
If the unit is to be shipped in an HP 9000 or  
10000 series rack:  
1. Remove the hex nuts, flat washers, and lock washers  
from the mounting rail.  
2. Install the rail reinforcement plates and tighten using the  
hex nuts with captive washers included in the kit, instead  
of the nuts included with the rail.  
3. Install the rear mounting brackets using hex nuts. Wait  
until the unit is installed and the brackets are adjusted  
before tightening the nuts.  
4. Insert screws through the mounting rail into the cage nuts  
or clip nuts.  
 
3. Install the mounting ears on the chassis using the  
Powering down the UPS  
screws provided.  
1. Shut down all load devices.  
2. Press the Standby button to take the UPS out of Operate  
mode. Power to the load receptacles ceases.  
3. Disconnect the UPS from utility power.  
4. Wait at least 60 seconds for the UPS internal circuitry  
to discharge.  
Switching off the ERM  
circuit breaker  
WARNING: To prevent personal injury from  
electric shock or damage to the equipment,  
verify that the circuit breaker is in the  
Off position.  
4. With one person on each side, lift the chassis to rail  
level and slide the chassis on the mounting rails.  
5. Attach the chassis to the rack using the supplied screws.  
6. If using the rear mounting brackets, be sure that the  
bracket tabs are fully inserted into the rear panel cutouts,  
then tighten the brackets.  
Attaching the ERM front bezel  
Installing the ERM  
Before installing the ERM, review and observe all warnings in  
WARNING: Uneven mechanical loading in  
the rack may cause a hazardous condition.  
CAUTION: Always plan the rack installation so that  
the heaviest item is on the bottom of the rack. Install  
the heaviest item first, and continue to populate the  
rack from the bottom to the top.  
2. With one person on each side of the carton, lift the  
chassis and lower it to the floor in front of the rack.  
 
Connecting the ERM to the UPS  
Configuring the UPS  
After the ERMs are installed, place the UPS in Configure  
mode, and use the UPS front panel controls and LED  
indicators to configure the UPS for the number of attached  
ERMs. Other UPS parameters that can also be configured  
are the nominal utility voltage level and Site Wiring  
Fault detection.  
In Configure mode, the LED front panel display changes  
function to enable modification of the UPS parameters. Each  
LED is associated with a different parameter.  
Available Parameter  
settings  
Associated Explanation (when LED is  
LED  
illuminated)  
Nominal  
Voltage  
Setting  
200/208  
Nom  
General  
Alarm  
(red)  
Nominal utility voltage  
level is set to 200/208  
VAC (factory default for  
326529-D71)  
NOTE: To install a second ERM, plug the cable from  
the second ERM into the socket at the rear of the first  
ERM. Up to two ERM units can be connected.  
220 Nom  
230 Nom  
On  
Battery  
(red)  
Nominal utility voltage  
level is set to 220 VAC  
Battery  
Nominal utility voltage  
Fault (red) level is set to 230 VAC  
(factory default for  
Switching on the ERM circuit breaker  
326529-B31)  
240 Nom  
Site  
Wiring  
Fault (red)  
Nominal utility voltage  
level is set to 240 VAC  
Wiring  
Fault  
Setting  
Wiring Fault Utility  
(green)  
Audible alarm sounds  
when ground is missing or  
line and neutral  
connections are reversed  
ERM  
Setting  
0 ERMs  
1 ERM  
2 ERMs  
0% to  
UPS is configured for no  
25% load attached ERMs (factory  
(green)  
default)  
26% to  
50% load attached ERM  
(green)  
UPS is configured for 1  
51% to  
UPS is configured for 2  
75% load attached ERMs  
(green)  
Charging the ERM batteries  
Connect the UPS to a grounded utility power outlet. When the  
UPS is plugged in, it automatically enters Standby mode and  
begins charging the ERM batteries. With the UPS in Standby  
mode, allow the ERM batteries to charge for at least 24 hours  
before putting the UPS into service.  
To change the UPS configuration parameters:  
1. Place the UPS in Configure mode.  
The LEDs associated with the currently configured  
parameters illuminate. A flashing green cursor indicates  
where you are in the configuration process as you scroll  
through the available settings.  
CAUTION: To ensure maximum runtime, be sure to  
configure the UPS for the number of installed ERMs  
using the UPS front panel controls.  
2. To change the nominal voltage, press the On button to  
advance the cursor to the LED associated with the  
appropriate nominal voltage parameter. The selected  
voltage configuration LED flashes.  
 
3. Press the Standby button to select the nominal voltage  
configuration. The LED associated with the old input  
voltage parameter turns off, and the LED associated with  
the new input voltage parameter illuminates solid green.  
UPS front panel LED indicators  
NOTE: Only one nominal utility voltage can be  
configured. When setting voltage configuration  
parameters, selecting an On value for any one  
parameter automatically sets the other possibilities  
to Off.  
4. To enable the Wiring Fault parameter, press the On  
button to advance the cursor to the Utility LED, then press  
the Standby button. The LED illuminates solid green.  
This parameter is disabled by default, and should only  
be enabled for line-to-neutral connections. Enabling this  
feature for line-to-line power sources causes a  
false alarm.  
The front panel is shown with the bezel removed.  
5. To configure the UPS for the number of connected ERMs,  
press the On button to advance the cursor to the load  
LED associated with the number of ERMs attached to  
the UPS.  
Item  
1
LED description  
Overload  
2
76% to 100% load  
51% to 75% load (2 ERMs)  
26% to 50% load (1 ERM)  
0% to 25% load (0 ERMs)  
General Alarm  
6. Press the Standby button to select the appropriate ERM  
configuration. The associated LED illuminates  
solid green.  
3
4
5
7. To save the configuration settings and exit Configure  
mode, press the Test/Alarm Reset button.  
6
7
On Battery  
NOTE: Configure mode times out after 2 minutes. If  
the Test/Alarm Reset button has not been pressed, any  
new selections are not saved.  
8
Battery Fault  
9
Site Wiring Fault  
Utility  
10  
11  
UPS front panel controls  
Configure Mode On  
For more information, see "LED and audible alarm  
troubleshooting" in the user guide.  
Legal notice  
© Copyright 2003, 2006 Hewlett-Packard Development Company, L.P.  
The information contained herein is subject to change without notice. The only  
warranties for HP products and services are set forth in the express warranty  
statements accompanying such products and services. Nothing herein should  
be construed as constituting an additional warranty. HP shall not be liable for  
technical or editorial errors or omissions contained herein.  
The front panel is shown with the bezel removed.  
Item Description  
Function  
1
2
3
On button  
Powers up the UPS  
Places the UPS in Standby mode  
Standby button  
Test/Alarm Reset  
button  
Silences UPS alarms  
Tests the LEDs  
4
Configure button  
Places the UPS in Configure mode  
 

Grizzly Power Hammer T10165 User Manual
Haier Washer HWM8000 User Manual
Hamilton Beach Cooktop Meal Maker User Manual
Healthrider Treadmill HRTL77105 User Manual
Hotpoint Electric Pressure Cooker 5TCG User Manual
HP Hewlett Packard PDAs Smartphones h4000 User Manual
Humax Car Satellite TV System LUG 17DS User Manual
Humminbird Fish Finder Wide Portrait User Manual
Hunter Fan Thermostat 47300A User Manual
IBM Laptop S30 User Manual