F111 Ceiling-Mounted
Commercial Media Air Cleaner
SPECIFICATION DATA
FEATURES
•
High Efficiency Particulate Air (HEPA) filter models are
99.97% efficient and the hospital grade particle filter
models are 95% efficient at 0.3 micron particles. Both
models are more efficient on particles smaller and
larger. There is also a 95% ASHRAE model.
•
•
Circulates up to 1230 cfm.
Provides Coanda airflow distribution by drawing air
from the room into the center of the room and
discharging the air to both ends of the room.
•
Designed to overcome the increase in airflow
resistance normally caused by filter loading.
•
•
White or black cover color complements ceiling color.
CPZ module removes VOC and space odors for up to
24 months.
APPLICATION
SPECIFICATIONS
The F111 Ceiling-Mounted Media Air Cleaner is designed for
use in commercial applications that require the removal of air-
borne particles and odors. Typical applications include
restaurants, bars, schools, offices, daycare centers, smoking
lounges, and any indoor space where people meet, work or
play. The F111 removes airborne particles such as dust, soot,
and some cooking smoke from the air circulated through the
filter.
Models: See Table 1.
Cabinet Material: Galvanized steel.
Color: White or black color cover available.
Electrical Ratings:
Input Power: 120V, 60 Hz, 6.5A; 277V, 60 Hz, 2.85A; and
208-230V, 50 Hz, 3.75A.
The F111 uses a single-speed, direct-drive, forward curve
blower motor with a high efficiency particulate arrestance
(HEPA) filter that provides high-efficiency removal of
particulates. When equipped with CPZ™ modules, the F111
also removes volatile organic compounds (VOC) and odor.
This high filtration and adsorption efficiency enables the F111
to remove many of the troublesome particles, gases and
odors from the indoor air.
Power Connection: Hard-wired.
Motor: 1/2 hp, PSC single-speed.
Airflow Pattern: F111 draws room air into center of room and
discharges air to both ends of room. This Coanda airflow
pattern scrubs room corners for improved air cleaning and
air circulation. See Fig. 1.
CEILING
Using the F111 to clean and recirculate indoor air can reduce
the amount of outside air required to meet the ASHRAE venti-
lation standard. This results in lower energy costs because
there is less outside air to condition.
FLOOR
M15587
Fig. 1. Airflow pattern.
The Honeywell Trademark is used under license from Honeywell Intellectual
Properties, Inc. by Air-Pure Systems.
Honeywell International Inc. makes no representations or warranties with
respect to this product.
68-3023-4
|