Honeywell Home Security System 4110XM User Manual

ADEMCO 4110XM  
SECURITY SYSTEM  
User Guide  
N5100V5 4/99 Rev. C  
 
TABLE OF CONTENTS  
System Overview.........................................................................................................................................5  
General ......................................................................................................................................................5  
Keypads .....................................................................................................................................................5  
Zones..........................................................................................................................................................5  
Alarms........................................................................................................................................................5  
Fire Protection...........................................................................................................................................6  
Burglary Protection...................................................................................................................................6  
Memory of Alarm.......................................................................................................................................6  
Pager Notification .....................................................................................................................................6  
About the Keypad ......................................................................................................................................7  
Keypad Styles ...........................................................................................................................................7  
Keypad Functions.......................................................................................................................................8  
Summary of System Status Displays.......................................................................................................8  
Summary of Keypad Functions ................................................................................................................9  
Security Codes...........................................................................................................................................11  
General ....................................................................................................................................................11  
Duress Code.............................................................................................................................................11  
Quick Arming ..........................................................................................................................................11  
Assigning, Changing or Deleting User Codes........................................................................................12  
Entry/Exit Delays......................................................................................................................................13  
General Information ...............................................................................................................................13  
Checking for Open Zones........................................................................................................................14  
Using the  
6
READY Key.....................................................................................................................14  
Arming The System .................................................................................................................................15  
Using The  
Using The  
Using The  
Using The  
3
7
2
4
STAY Key .......................................................................................................................15  
INSTANT Key ................................................................................................................16  
AWAY Key.......................................................................................................................17  
MAXIMUM Key...............................................................................................................18  
Disarming and Silencing Alarms .........................................................................................................19  
– 3 –  
 
(continued)  
TABLE OF CONTENTS  
Using the  
1
OFF Key............................................................................................................................19  
To Disarm the System..................................................................................................................................19  
To Silence a Burglary Alarm ..................................................................................................................19  
Bypassing Protection Zones...................................................................................................................20  
Using The  
6
BYPASS Key.........................................................................................................................20  
Quick Bypass...........................................................................................................................................21  
Using the Keyswitch.................................................................................................................................22  
General ....................................................................................................................................................22  
Arming.....................................................................................................................................................22  
Disarming................................................................................................................................................22  
Chime Mode................................................................................................................................................23  
Using the  
9
CHIME Key......................................................................................................................23  
Panic Keys ..................................................................................................................................................24  
Using Panic Keys ....................................................................................................................................24  
Testing the System ...................................................................................................................................26  
Using the  
5
TEST Key..........................................................................................................................26  
Trouble Conditions...................................................................................................................................27  
"Check" and "Battery" Displays..............................................................................................................27  
Power Failure ..........................................................................................................................................27  
Other Displays.........................................................................................................................................28  
Fire Alarm System....................................................................................................................................29  
General ....................................................................................................................................................29  
In Case of Fire Alarm..............................................................................................................................29  
Silencing Fire Alarms .............................................................................................................................30  
National Fire Protection Association Recommendations on Smoke Detectors....................................31  
Emergency Evacuation ...........................................................................................................................32  
Quick Guide to Alarm System Functions ............................................................................................33  
Summary of Audible/Visual Notification ............................................................................................34  
Protection Zones List...............................................................................................................................35  
Owner's Insurance Premium Credit Request ....................................................................................36  
Regulatory Statements and Warnings .................................................................................................38  
In The Event of Telephone Operational Problems............................................................................40  
Limitations of this Alarm System .........................................................................................................41  
Servicing Information .............................................................................................................................42  
Two Year Limited Warranty...................................................................................................................43  
4
 
System Overview  
General  
This system offers you three forms of protection: burglary, fire and emergency. Your  
system may consist of at least one keypad which provides full control of system  
operation, various sensors such as motion detectors and door and window sensing  
devices, plus a selected number of strategically placed smoke or combustion detectors  
designed to provide early warning in case of fire. Your system may also have been  
programmed to automatically transmit alarm or status messages over the phone  
lines to a central alarm monitoring station.  
Keypads  
All system functions are controlled by your keypad(s). The keypads feature a  
telephone style (digital) keypad and a Liquid Crystal Display (LCD) which shows the  
nature and location of all occurrences. Their built-in sounder will sound during alarm  
and trouble conditions.  
For additional information, see the following section: ABOUT THE KEYPAD.  
Zones  
Your system's sensing devices have been assigned to various zones. For example, the  
sensing device on your Entry/Exit door may have been assigned to zone 01, sensing  
devices on windows in the master bedroom to zone 02, and so on. These zone numbers  
will appear on the display when an alarm or trouble condition occurs.  
Alarms  
When an alarm occurs, both the keypad and external sounders will sound, and a mes-  
sage at the keypad will identify the zone(s) causing the alarm. In addition, if your  
system is connected to a central monitoring station, an alarm message will be sent.  
To stop the alarm sounding, you simply disarm the system.  
– 5 –  
 
System Overview (cont’d)  
Fire Protection  
The fire protection portion of your security system (if used) is always on and will  
sound an alarm if a fire condition is detected. Refer to the FIRE ALARM SYSTEM  
section for important information concerning fire protection, smoke detectors and  
planning emergency exit routes from your premises.  
Burglary Protection  
The burglary protection portion of your system must be turned on or "armed" before  
it will sense burglary alarm conditions and sound an alarm. Your system can be  
armed in one of four modes: STAY, AWAY, INSTANT and MAXIMUM. Refer to the  
ARMING THE SYSTEM sections for instructions in using these modes of operation.  
Your system also provides a CHIME mode for alerting you to the opening and closing  
of doors and windows while the system is disarmed.  
Memory of Alarm  
When an alarm or trouble condition occurs, the keypad displays the number(s) of the  
zone(s) that caused the problem, and displays the type of alarm or trouble (ex. FIRE,  
ALARM, CHECK). The display remains until it is cleared by entering the OFF  
sequence (security code + OFF key) twice.  
Pager Notification  
If you have chosen to be notified of alarms or other system conditions by pager, the  
following codes will be sent to your pager by the control:  
1811=Trouble  
1001=Open  
1911=Alarm  
1002=Close  
6
 
About the Keypad  
Keypad Styles  
The 6150 is a Fixed-Word keypad. The keys on the keypads are located behind a flip-down  
door which can be removed, if desired.  
ARMED  
READY  
OFF  
MAX  
AWAY  
TEST  
CODE  
STAY  
3
BYPASS  
6
CHIME  
9
#
1
4
7
2
5
8
0
INSTANT  
READY  
SHOWN WITH DOOR REMOVED  
– 7 –  
 
About the Keypad (cont’d)  
SUMMARY OF SYSTEM STATUS DISPLAYS  
AWAY  
STAY  
All burglary zones, interior & perimeter, are  
armed.  
Perimeter burglary zones, such as windows  
and doors are armed.  
NO AC  
AWAY  
BYPASS  
NOT READY  
CHIME BAT  
ALARM STAY  
CHECK INSTANT  
FIRE  
INSTANT  
BYPASS  
Perimeter burglary zones armed and entry  
delay is turned off.  
style B_disp.  
One or more burglary protection zones have  
been bypassed.  
NOT READY Appears when burglary portion of the system  
is not ready for arming (due to one or more  
open protection zones).  
FIXED-WORD KEYPAD  
DISPLAY  
READY  
The burglary portion of the system is ready to  
be armed.  
NO AC  
Appears when AC power has been cut off.  
System is operating on backup battery power.  
AC  
CHIME  
BAT  
Appears when AC power is present.  
Appears when the CHIME feature is ON.  
Low system battery.  
ALARM  
Appears when an intrusion has been detected  
and the system is armed (also appears during  
a fire alarm). Accompanied by the ID # of the  
protection zone in alarm.  
CHECK  
FIRE  
Appears when a malfunction is discovered in  
the system at any time or if a fault is detected  
in a FIRE zone at any time or in a DAY  
(Trouble)/NIGHT (Alarm) burglary zone  
during a disarmed period. Accompanied by a  
display of zone number in trouble.  
Appears when a fire alarm is present.  
Accompanied by a display of the zone in  
alarm.  
8
 
Keypad Functions  
SUMMARY OF KEYPAD FUNCTIONS  
1. DISPLAY WINDOW: Displays protection  
8.  
7
INSTANT KEY: Arms in manner  
zone ID and system status messages.  
similar to STAY mode, but without  
the entry delay feature. Entering via  
the entry/exit door will cause an  
instant alarm.  
2.  
1
OFF KEY: Disarms burglary portion  
of the system, silences alarms and  
audible trouble indicators, and  
clears visual display after problem's  
correction.  
9.  
8
9
CODE KEY: Used to assign  
additional user codes for other users  
of the system.  
3.  
4.  
2
3
AWAY KEY: Arms the entire  
burglary system, perimeter and  
interior.  
10.  
CHIME KEY: Turns CHIME mode on  
and off. When on, the opening of  
windows or doors while the system is  
disarmed will sound 3 beeps at the  
keypad(s).  
STAY KEY: Arms perimeter portion  
of burglary system only. Interior  
protection is not armed, which  
allows movement within premises  
without causing alarm.  
11.  
12.  
6
READY KEY: Displays all open  
protection zones.  
5.  
4
MAXIMUM KEY: Arms in manner  
#
KEY: "Quick Arm" key permits  
similar to AWAY mode, but without  
the entry delay feature, thus provid-  
ing maximum protection. An alarm  
will occur immediately upon  
ARMING of the system without use of  
a security code (if so programmed).  
13. KEYS 0–9 : Used to enter your security  
code(s).  
opening any protection point,  
14. READY INDICATOR: (GREEN) Lit when  
the system is ready to be armed (no faults  
present). While the system is disarmed,  
this indicator will go on and off as  
including the entry/exit door.  
6.  
7.  
5
6
TEST KEY: Tests the system and  
alarm sounder if disarmed. Refer to  
TESTING THE SYSTEM section  
for test procedures.  
protection zones are closed and opened.  
Note: On some keypads a POWER INDICATOR  
(GREEN) is lit when AC power is present. If  
the indicator is off, the system may still be  
operating, but on its backup battery power.  
See Power Failure in TROUBLE CONDITIONS  
section.  
BYPASS KEY: Removes individual  
protection zones from being  
monitored by the system.  
– 9 –  
 
Keypad Functions (cont’d)  
15. ARMED INDICATOR: (RED) Lit when  
4
1
2
3
the system has been armed (STAY,  
AWAY, INSTANT or MAXIMUM).  
16  
16. INTERNAL SOUNDER: The built-in  
keypad sounder mimics the alarm  
sounder during alarms, and will also  
"beep" during certain system functions.  
(see SUMMARY OF AUDIBLE/  
VISUAL NOTIFICATION).  
15  
5
6
ARMED  
READY  
OFF  
MAX  
AWAY  
STAY  
3
BYPASS  
6
CHIME  
9
#
A
B
C
1
4
7
2
5
8
0
TEST  
7
INSTANT  
READY  
CODE  
14  
10  
17. EMERGENCY KEYS:  
Individual keys A, B, and C (key D not  
used). On some keypads, these keys are  
not present, and the following key pairs  
may be available, instead, for  
12  
11  
8
9
13  
17  
6150-007-V0  
emergency functions:  
6 & # ,  
6
& 1 ,  
#
& 3  
Some or all of these keys/pairs may be  
programmed for panic functions by your  
installer (see PANIC KEYS section).  
IMPORTANT! When entering codes and  
commands, sequential key depressions must  
be made within 2 seconds of one another. If 2  
seconds elapses without a key depression,  
the entry is aborted and must be repeated  
from its beginning.  
Note: Keys 1 through 9 each perform their associated companion functions (OFF, AWAY, STAY,  
etc.) when preceded by an entry of the security code (as described later).  
10  
 
Security Codes  
General  
At the time of installation, your installer programmed a personal four-digit Master  
code, known only to you and yours. This code is used to perform most system  
functions, including arming and disarming of the system. As an additional safety  
feature, temporary user codes can be assigned (see next page) for use by those not  
having a need to know the Master code. Note that the Master code remains in effect  
even when other user codes are assigned.  
Duress Code  
Ask your installer if "Duress" is active for your system. If so, check here:  
This feature is intended for use when you are forced to disarm or arm the system  
under threat. When used, the system will act normally, but can silently notify the  
central station of your situation, if that service has been provided.  
The Duress code is defined as User number 8.  
Important: The Duress code is useful only when connected to a central station.  
Quick Arming  
Ask your installer if "Quick Arming" is active for your system. If so, check here:  
If your system supports "Quick Arming", the "#" key can be pressed in place of the  
security code when arming the system. The security code is always required,  
however, when disarming the system.  
– 11 –  
 
Security Codes (cont’d)  
Assigning, Changing, or Deleting User Codes  
4-DIGIT USER CODES  
It is recommended that obvious codes  
such as 1 1 1 1 or 1 2 3 4 not be  
assigned.  
1. Enter your Master code and press the CODE key.  
2. Enter single-digit user number ('2', '3', '4', '5', '6' or '7') for which a code is to be  
assigned, changed, or deleted.  
3. If assigning or changing a user's code, enter the desired 4-digit code for use  
by that user number. The keypad will beep once.  
If deleting a user's code, perform steps 1 & 2 and stop. In a few moments the  
keypad will beep once, indicating that the existing code has been deleted.  
To assign your Duress code, perform the following:  
Enter your [Master code] + [8] + [8] + [desired 4-digit code]. The keypad will  
beep once.  
The Master code can be changed by the main user of the system. To change it,  
perform the following:  
Enter your [Master code] + [8] + [1] + [new Master code] + [new Master code]  
again. The keypad will beep once.  
Important: Temporary users should not be shown how to use any system function  
they do not need to know (e.g., bypassing protection zones).  
12  
 
Entry/Exit Delays  
General Information  
Your system has preset time delays, known as exit delay and entry delay. When you  
arm your system, exit delay gives you time to leave through the entry/exit door  
without setting off an alarm. Entry delay gives you time to disarm the system when  
you re-enter through the entry/exit door. The system must be disarmed, however,  
before the entry delay period ends, or an alarm will occur. The keypad will beep  
slowly during the entry delay period, reminding you to disarm the system.  
You can also arm the system with no entry delay at all by using either INSTANT or  
MAXIMUM arming modes. These modes can provide greater security while you are  
sleeping or while you are away for extended periods of time.  
See your installer for your delay times and record them here:  
Exit Delay:  
seconds  
seconds  
Entry Delay:  
– 13 –  
 
Checking for Open Zones  
Using the  
6
READY Key  
Before your system can be armed, all protected doors, windows and other protection  
zones must be closed or bypassed (see BYPASSING PROTECTION ZONES section),  
otherwise the keypad will display a "Not Ready" message, and if your keypad has a  
READY indicator light, it will not be lit. The READY key can be used to display all  
faulted zones, making it easier for you to secure any open zone.  
To display faulted zones, simply press and release the READY key (do not enter code  
first). Secure or bypass the zones displayed before arming the system.  
A "Ready" message will be displayed when all protection zones have been either  
closed or bypassed and the keypad's READY indicator light (if present) will be lit.  
TYPICAL DISPLAYS  
WHEN NOT READY TO ARM  
AC  
NOT READY  
4110-002-V0  
INDICATING FAULTED PROTECTION ZONE  
(AFTER PRESSING READY KEY)  
AC  
NOT READY  
4110-003-V0  
INDICATING "READY TO ARM"  
AC  
4110-004-V0  
14  
 
Arming the System  
Using the  
3
STAY Key (Arms Perimeter Only, Entry Delay On)  
Use this key when you are staying inside, but expect someone to use an  
entry/exit door later.  
Before Arming close all doors and windows (see CHECKING FOR OPEN ZONES).  
1. Enter your security code and press the STAY key.  
2. The keypad will beep three times and will display the armed message. The red  
ARMED indicator will light.  
3. The system will arm. An alarm will sound immediately if a protected perimeter  
window or non-entry/exit door is then opened, but you may otherwise move freely  
throughout the premises.  
Later arrivals can enter through an entry/exit door without causing an alarm, but  
they must disarm the system within the entry delay period to avoid sounding an  
alarm.  
TYPICAL DISPLAY  
"ARMED STAY"  
AC  
STAY  
FIXED-WORD  
– 15 –  
 
Arming the System (cont’d)  
Using the  
7
INSTANT Key (Arms Perimeter Only, Entry Delay Off)  
Use this key when you are staying inside, and do not expect anyone to use  
an entry/exit door.  
Before Arming close all doors and windows (see CHECKING FOR OPEN ZONES).  
1. Enter your security code and press the INSTANT key.  
2. The keypad will beep three times and will display the armed message. The red  
ARMED indicator will light.  
3. The system will arm. An alarm will sound immediately if any protected perimeter  
window or door is then opened, but you may otherwise move freely throughout the  
premises.  
An alarm will sound immediately if anyone opens an entry/exit door.  
TYPICAL DISPLAY  
"ARMED INSTANT"  
AC  
STAY  
INSTANT
FIXED-WORD  
16  
 
Arming the System (cont’d)  
Using the  
2
AWAY Key (Arms Entire System, Entry Delay On)  
Use this key when no one will be staying inside.  
Before Arming close all doors and windows (see CHECKING FOR OPEN ZONES).  
1. Enter your security code and press the AWAY key.  
2. The keypad will beep twice and will display the armed message. The red ARMED  
indicator will light.  
3. You may leave through an entry/exit door during the exit delay period without  
causing an alarm.  
After exit delay, the system arms and will sound an alarm if a protected window or  
non-entry/exit door is then opened, or if any movement is detected inside your  
premises.  
You may reenter through an entry/exit door, but must disarm the system within the  
entry delay period to avoid an alarm.  
TYPICAL DISPLAY  
"ARMED AWAY"  
AC  
AWAY  
FIXED-WORD  
– 17 –  
 
Arming the System (cont’d)  
Using the  
4
MAXIMUM Key (Arms Entire System, Entry Delay OFF)  
Use this key when the premises will be vacant for extended periods of time  
such as vacations, etc, or when no one will be moving through protected  
areas.  
Before Arming close all doors and windows (see CHECKING FOR OPEN ZONES).  
1. Enter your security code and press the MAX key.  
2. The keypad will beep twice and will display the armed message. The red ARMED  
indicator will light.  
3. You may leave through an entry/exit door during the exit delay period without  
causing an alarm.  
After exit delay, the system arms and will sound an alarm if a protected window or  
door is then opened, or if any movement is detected inside your premises.  
An alarm will sound immediately if anyone opens an entry/exit door.  
TYPICAL DISPLAY  
"ARMED MAXIMUM"  
AC  
AWAY  
INSTANT
FIXED-WORD  
18  
 
Disarming and Silencing Alarms  
Using the  
1
OFF Key  
The OFF key is used to disarm the system and to silence alarm and trouble sounds.  
IMPORTANT: If you return and the main burglary sounder is on: DO NOT  
ENTER, but CONTACT THE POLICE from a nearby safe location.  
If you return after an alarm has occurred and the main sounder has shut  
itself off: the keypad will beep rapidly upon your entering, indicating that an alarm  
has occurred during your absence (the Memory of Alarm feature).  
LEAVE IMMEDIATELY and CONTACT THE POLICE from a nearby safe location.  
WHEN SAFE TO DO SO, re-enter and follow the procedure for silencing an alarm.  
To Disarm the System  
Enter your security code and press the OFF key. The "Ready" message will be  
displayed, and the keypad will emit a single tone to confirm that the system is  
disarmed.  
To Silence a Burglary Alarm  
Enter your security code and press the OFF key to silence the alarm (or warning  
tones of a Memory of Alarm). Note the zone in alarm on the keypad display, and  
make that zone intact (close door, window, etc.). Now enter the security code plus  
OFF sequence again to clear the keypad's Memory of Alarm display. If the display  
will not clear and does not provide a "Ready" message, notify the alarm agency.  
To Silence a Fire Alarm simply press the OFF key (the security code is not needed to  
silence FIRE alarms). To then clear the keypad's Memory of Alarm display, enter  
your security code and press the OFF key again.  
Refer to the Fire Alarm System section for additional information.  
Refer to the Summary of Audible/Visual Notification section for information  
which will help you to distinguish between FIRE (Interrupted/Pulsed) and  
BURGLARY (Continuous/Steady) alarm sounds.  
– 19 –  
 
Bypassing Protection Zones  
Using the  
6
BYPASS Key  
This key is used when you want to arm your system with one or more zones  
intentionally unprotected. The system must be disarmed first.  
When bypassing zones:  
The system will not allow fire zones to be bypassed.  
All bypasses are removed when an OFF sequence (security code plus OFF) is  
performed.  
Bypassed zones are unprotected and will not cause an alarm if violated while  
your system is armed.  
1. Enter your security code and press the BYPASS key.  
2. Enter zone number(s) for the zone(s) to be bypassed (e.g., 06, 10, 13, etc.). Single  
digit zone numbers must be preceded by a zero (e.g. 05, 06).  
3. When finished, the keypad will display a "Bypass" message along with each by-  
passed zone number, accompanied by a beep for each. Wait for these zones to be  
displayed, to confirm their bypass.  
4. Arm the system as usual.  
TYPICAL MOMENTARY DISPLAY  
OF BYPASSED ZONE  
AAC  
BYPASS  
4110-001-V0  
FIXED-WORD  
20  
 
Bypassing Protection Zones (cont’d)  
Quick Bypass  
Ask your installer if "Quick Bypass" is active for your system, and if so, check here:  
If your system supports "Quick Bypass," it allows you to easily bypass all open  
(faulted) zones without having to enter zone numbers individually.  
To use this feature, enter your security code, press the BYPASS key, then stop. In a  
few moments, all open zones will be displayed along with a "Bypass" message. Wait  
for all bypassed zones to be displayed, then arm the system as usual.  
TYPICAL DISPLAY  
"READY TO ARM WITH ZONES BYPASSED"  
AC  
BYPASS  
FIXED-WORD  
– 21 –  
 
Using the Keyswitch  
General  
Your system may be equipped with a keyswitch for use when arming and disarming.  
A single red light on the keyswitch plate indicates the status of your system as  
follows:  
OFF = Disarmed, Not Ready for Arming  
SLOW FLASHING = Disarmed, Ready for Arming  
RAPID FLASHING = Armed STAY or AWAY  
Arming  
To arm in the AWAY mode, turn key to right for 1/2 second.  
To arm in the STAY mode, hold key turned to right for more than one second.  
The keypads will beep twice (AWAY mode) or 3 times (STAY mode) and the  
keyswitch light will flash rapidly.  
Disarming  
To disarm the system, turn the key to the right and release.  
If an alarm has occurred during the armed period, the keyswitch's light will not flash  
on disarming (thus indicating memory of an alarm). With some controls, turning the  
keyswitch key to the right a second time after disarming can clear the alarm from  
memory, but it is advisable, instead, to refer to a keypad to diagnose and clear any  
problem, and to subsequently clear alarm memory.  
22  
 
Chime Mode  
Using the  
9
CHIME Key  
This feature can be used only while the burglary system is disarmed.  
Your system can be set to alert you to the opening of a door or window while it is dis-  
armed by using CHIME mode. When activated, three tones will sound at the Keypad  
whenever a protected door or window is opened. Pressing the READY key will  
display the open points.  
To turn Chime Mode on:  
Enter the security code and press the CHIME key. The CHIME message will  
appear.  
To turn Chime Mode off:  
Enter the security code and press the CHIME key again. The CHIME message will  
disappear.  
– 23 –  
 
Panic Keys  
Using Panic Keys  
Your system may have been programmed to use special keys or combinations of keys  
to manually activate emergency (panic) functions. The functions that might be  
programmed are: Silent Emergency, Audible Emergency, Personal Emergency, and  
Fire.  
To activate a Panic Function  
Press an active lettered key for at least two seconds.  
OR  
Press both keys of an active pair at the same time.  
A silent emergency will send a silent alarm signal to the central station*, but there  
will be no audible alarms or visual displays.  
An audible emergency will send a signal to the central station* and sound a loud,  
steady alarm at your keypad(s) and at any external sounders that may be connected  
(ALARM plus a zone number would also be displayed).  
A personal emergency alarm will send an emergency message to the central  
station* and will sound at keypad(s), but not at external bells or sirens.  
A fire alarm will send a fire alarm message to the central station* and will uniquely  
sound at keypad(s) and external bells and sirens (FIRE plus a zone number would  
also be displayed).  
* If connected  
24  
 
Panic Keys (cont’d)  
1 & *  
A
B
C
D
OFF  
AWAY  
STAY  
1
2
3
MAX  
TEST BYPASS  
3 & #  
LETTERED  
EMERGENCY  
KEYS  
4
5
6
<
PAIRED  
EMERGENCY  
KEYS  
INSTANT CODE CHIME  
("D" IS  
NOT USED)  
>
7
8
9
READY  
0
#
TYPICAL  
KEYPAD  
*
* & #  
CHECK  
IF  
ACTIVE  
PROGRAMMED  
FUNCTION  
ZONE  
PANIC  
KEY(S)  
NUMBER  
[A]  
SILENT EMERGENCY (Fixed-Function)  
95  
07  
96  
SEE YOUR  
[B]  
____SILENT, ____AUDIBLE, ____PERSONAL, ____FIRE  
AUDIBLE EMERGENCY (Fixed-Function)  
INSTALLER AND  
NOTE THE KEY(S) &  
FUNCTION(S)  
[C]  
OR  
[1] & [6]  
SILENT EMERGENCY (Fixed-Function)  
95  
PROGRAMMED  
FOR YOUR SYSTEM  
[/] & [#]  
____SILENT, ____AUDIBLE, ____PERSONAL, ____FIRE  
AUDIBLE EMERGENCY (Fixed-Function)  
07  
96  
[3] & [#]  
• KEYS [A], [B], AND [C] ARE NOT PRESENT ON ALL KEYPADS.  
• KEY [D], IF PRESENT ON YOUR KEYPAD, IS NOT ACTIVE HERE.  
– 25 –  
 
Testing the System  
Using the  
5
TEST Key  
The TEST key puts your system into Test mode, which allows each protection point  
to be checked for proper operation. Testing should be conducted weekly to ensure  
proper operation.  
NO ALARM REPORTS WILL BE SENT TO THE CENTRAL MONITORING STATION while the  
system is in Test mode.  
1. Disarm the system and close all protected windows, doors, etc. The keypad's  
READY message should be displayed and the READY indicator (if present)  
should be lit.  
2. Enter your security code and press the TEST key.  
3. The keypad will sound a single beep every 40 seconds as a reminder that the  
system is in the test mode.  
Each time a protection zone is faulted, the external siren or bell should sound for one  
second and then turn off, while the keypad sounds 3 beeps. If this does not happen,  
call for service immediately.  
4. Open and close each protected door and window in turn and listen for the  
required sounds. The identification of each faulted protection point should appear  
on the display.  
5. Walk in front of any interior motion detectors (if used) and listen for the required  
sound as movement is detected. The identification of the detector should appear  
on the display when it is activated.  
6. Follow the manufacturer's instructions to test all smoke detectors, to ensure that  
all are functioning properly. The identification of each detector should appear on  
the display when each is activated.  
7. After all protection points have been checked and restored, there should be no  
zone identification numbers displayed. If a problem is experienced with any  
protection point (no confirming sounds, no display), CALL FOR SERVICE  
IMMEDIATELY.  
8. Turn off the Test mode by entering the security code and pressing the OFF key.  
26  
 
Trouble Conditions  
"Check" and "Battery" Displays  
The word CHECK on the keypad's display, accompanied by a "beeping" at the  
keypad, indicates a trouble condition in the system.  
To silence the beeping for these conditions, press any key.  
1. A display of "CHECK" and one or more zone numbers indicates that a  
problem exists with the displayed zone(s) and requires your attention. If the  
CHECK display relates to a fire zone, CALL FOR SERVICE  
IMMEDIATELY.  
2. Determine if the zone(s) displayed are intact and make them so if they are not. If  
the problem has been corrected, the display can be cleared if you enter the OFF  
sequence (user code plus OFF key) twice. If the display persists, CALL FOR  
SERVICE IMMEDIATELY.  
TYPICAL "CHECK" DISPLAY  
AC  
03  
CHECK
FIXED-WORD  
3. A display of "BAT" with no zone number or beeping indicates that the main  
standby battery in your control is weak. If this condition persists for more  
than one day (with AC present), CALL FOR SERVICE.  
Power Failure  
If there is no keypad display at all, and the POWER indicator (if present) is  
not lit, operating power for the system has stopped and the system is inoperative.  
CALL FOR SERVICE IMMEDIATELY.  
If the message "AC LOSS" or "NO AC" is displayed, and the POWER indicator  
(if present) is off, the Keypad is operating on battery power only. If only some lights  
are out on the premises, check circuit breakers and fuses and reset or replace as  
necessary. CALL FOR SERVICE IMMEDIATELY if AC power cannot be  
restored.  
27  
 
Trouble Conditions (cont’d)  
Other Displays  
dl: If this remains displayed for more than 1 minute, your system is disabled.  
CALL FOR SERVICE IMMEDIATELY.  
CC: The system is in communication with the central station for change of function  
or status verification. If this message persists for more than 10 minutes,  
CALL YOUR SERVICE COMPANY.  
FC: A communication failure has occurred. CALL FOR SERVICE  
IMMEDIATELY.  
OC The keypad is not receiving signals from the control panel and sees an open cir-  
cuit. If this message persists for more than 10 minutes, CALL YOUR  
SERVICE COMPANY.  
28  
 
Fire Alarm System  
IF INSTALLED  
General  
Your fire alarm system (if installed) is on 24 hours a day, for continuous protection.  
In the event of an emergency, the strategically located smoke and heat detectors will  
automatically send signals to your system, triggering a loud, interrupted sound from  
the Keypad. An interrupted sound will also be produced by optional exterior  
sounders. A FIRE message will appear at your Keypad and remain on until you  
silence the alarm.  
In Case Of Fire Alarm  
1. Should you become aware of a fire emergency before your detectors sense the  
problem, go to your nearest Keypad and manually initiate an alarm by pressing  
the panic key pair assigned as FIRE emergency (if programmed by the installer).  
See the “PANIC KEYS” section.  
2. Evacuate all occupants from the premises.  
3. If flames and/or smoke are present, leave the premises and notify your local Fire  
Department immediately.  
4. If no flames or smoke are apparent, investigate the cause of the alarm. The zone  
number(s) of the zone(s) in an alarm condition will be displayed at the Keypad.  
TYPICAL "FIRE EMERGENCY" DISPLAY  
AC  
05  
ALARM  
FIRE  
FIXED-WORD  
– 29 –  
 
Fire Alarm System (cont’d)  
Silencing Fire Alarms  
1. Silence the alarm by pressing the OFF key (security code not needed to silence  
fire alarms). To clear the display, enter your code and press the OFF key again  
(Memory of Alarm).  
2. If the Keypad does not indicate a READY condition after the second OFF  
sequence, press the READY key to display the zone(s) that are faulted. Be sure  
to check that smoke detectors are not responding to smoke or heat producing  
objects in their vicinity. Should this be the case, eliminate the source of heat or  
smoke.  
3. If this does not remedy the problem, there may still be smoke in the detector.  
Clear it by fanning the detector for about 30 seconds.  
4. When the problem has been corrected, clear the display by entering your code  
and pressing the OFF key.  
30  
 
Fire Alarm System (cont’d)  
National Fire Protection Association Recommendations on  
Smoke Detectors  
General  
With regard to the number and placement of smoke/heat detectors, we subscribe to  
the recommendations contained in the National Fire Protection Association's  
Standard #74 noted below.  
Early warning fire detection is best achieved by the installation of fire detection  
equipment in all rooms and areas of the premises as follows: A smoke detector  
installed outside of each separate sleeping area, in the immediate vicinity of the  
bedrooms and on each additional story of the family living unit, including basements  
and excluding crawl spaces and unfinished attics.  
In addition, it is recommended that the owner consider the use of heat or smoke  
detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic,  
furnace room, utility and storage rooms, basements and attached garages.  
KITCHEN  
KITCHEN  
LIVING ROOM  
BDRM  
DINING  
BEDROOM  
BEDROOM  
TV ROOM  
DINING  
BDRM  
BEDROOM  
BEDROOM  
LIVING ROOM  
Smoke Detectors for Minimum Protection  
Smoke Detectors for Additional Protection  
Heat-Activated Detectors  
BEDROOM  
TO  
BR  
BEDROOM  
BEDROOM  
KTCHN  
GARAGE  
CLOSED  
DOOR  
LVNG RM  
.
BASEMENT  
floor_plan-001-V1  
– 31 –  
 
Fire Alarm System (cont’d)  
Emergency Evacuation  
Establish and regularly practice a plan of escape in the event of fire. The following  
steps are recommended by the National Fire Protection Association:  
Steps to Safety  
1. Plan on your detector or your interior and/or exterior  
sounders warning all occupants.  
2. Determine two means of escape from each room. One path  
2nd FLOOR  
of escape should lead to the door that permits normal exit  
from the building. The other may be a window, should  
your path be unpassable. Station an escape ladder at such  
windows if there is a long drop to the ground.  
BACK DOOR  
3. Sketch a floor plan of the building. Show windows, doors,  
stairs and rooftops that can be used to escape. Indicate  
escape routes for each room. Keep these routes free from  
1st FLOOR  
obstruction and post copies of the escape routes in every  
room.  
4. Assure that all bedroom doors are shut while you are  
asleep. This will prevent deadly smoke from entering  
while you escape.  
5. Try the door. If the door is hot, check your alternate  
escape route. If the door is cool, open it cautiously. Be  
BACK  
prepared to slam the door if smoke or heat rushes in.  
6. Crawl in the smoke and hold your breath.  
7. Escape quickly; don't panic.  
8. Establish a common meeting place outdoors, away from  
your premises, where everyone can meet and then take  
steps to contact the authorities and account for those  
FRONT  
missing. Choose someone to assure that nobody returns to  
the premises — many die going back.  
32  
 
Quick Guide to Basic System Functions  
FUNCTION  
Check Zones  
Arm System  
PROCEDURE  
Press READY key.  
COMMENTS  
To view faulted zones when system not ready.  
Arms system in mode selected.  
Enter code. Press arming key desired:  
(AWAY, STAY, INSTANT, MAXIMUM)  
Press #. Press arming key desired:  
(AWAY, STAY, INSTANT, MAXIMUM)  
Quick Arm  
Arms system in mode selected, quickly and  
without use of code.  
(if programmed)  
Bypass Zone(s)  
Enter code. Press BYPASS key.  
Enter zone number(s) to be bypassed  
(use 2-digit entries).  
Bypassed zones are unprotected and will not  
cause an alarm if violated.  
Quick Bypass  
(if programmed)  
Silence Sounders  
Burglary:  
Enter code. Press BYPASS key.  
Bypasses all faulted zones automatically.  
Enter code. Press OFF key.  
Press OFF key.  
Also disarms system. Memory of alarm remains  
until cleared.  
Fire:  
Memory of Alarm remains until cleared.  
"Check":  
Press any key.  
Determine cause. see “Check” and “Battery”  
Displays under TROUBLE CONDITIONS.  
Disarm System  
Enter code. Press OFF key.  
Also silences sounders. Memory of alarm  
remains until cleared.  
Clear Alarm  
Memory  
After disarming, enter code again.  
Press OFF key again.  
Keypad will beep rapidly upon entry if alarm  
has occurred.  
Alarm display will remain upon disarming until  
cleared.  
Duress  
(if connected to  
central station)  
Enter user code 8 to arm or disarm "normally."  
Performs desired action and sends silent alarm  
to central station.  
Panic Alarms  
(as programmed)  
Press key [A], [B], or [C] for at least 2 sec., or  
(if no A, B, or C on your keypad)  
press keys [1]&[6], or [6]&[#], or [3]&[#],  
both at same time.  
See “PANIC KEYS” for functions programmed  
for your system.  
Chime Mode  
Test Mode  
To turn ON or OFF: Enter code. Press CHIME  
key.  
Keypad will sound if doors or windows are  
violated while system is disarmed and chime  
mode is ON.  
To turn ON: Enter code. Press TEST key.  
To turn OFF: Enter code. Press OFF key.  
Tests alarm sounder and allows sensors to be  
tested.  
– 33 –  
 
Summary of Audible/Visual Notification  
SOUND  
LOUD, INTERRUPTED  
Keypad & External  
CAUSE  
FIRE ALARM  
DISPLAY  
FIRE and ALARM are displayed; protection zone in alarm  
is displayed.  
BURGLARY/AUDIBLE  
EMERGENCY ALARM  
a. SYSTEM DISARM  
ALARM is displayed; protection zone in alarm is also  
displayed.  
LOUD, CONTINUOUS  
Keypad & External  
ONE SHORT BEEP  
(not repeated)  
Keypad only  
a. Only READY is displayed. Green READY indicator (if  
present) is lit.  
b. NOT READY is displayed, open protection zone number  
is displayed.  
Green READY indicator (if present) is not lit.  
b. SYSTEM ARMING ATTEMPT  
WITH AN OPEN ZONE  
c. The bypassed protection zone numbers are displayed.  
(One beep for each number displayed.) BYPASS  
displayed.  
c. BYPASS VERIFY  
ONE SHORT BEEP  
SYSTEM IS IN TEST MODE  
Opened Zone identifications will appear.  
(once every 40 seconds)  
Keypad only  
ONE BEEP every 40 sec. TROUBLE  
Keypad only  
CHECK displayed. Troubled protection zone is displayed.  
AWAY and (if MAXIMUM) INSTANT are displayed.  
TWO SHORT BEEPS  
Keypad only  
ARM AWAY OR MAXIMUM  
THREE SHORT BEEPS  
Keypad only  
a. ARM STAY OR INSTANT  
a. STAY and (if INSTANT) INSTANT are displayed. Red  
ARMED indicator is lit.  
b. CHIME displayed. Pressing ./ READY key will display  
opened zone.  
b. ZONE OPENED WHILE SYS-  
TEM IS IN CHIME MODE  
c. Open protection zone number is displayed.  
c. ZONE OPENED WHILE SYS-  
TEM IS IN TEST MODE  
RAPID BEEPING  
Keypad only  
MEMORY OF ALARM  
FIRE and/or ALARM is displayed; zone in alarm is  
displayed.  
SLOW BEEPING  
Keypad only  
ENTRY DELAY WARNING  
None during delay; Exceeding the delay time without  
disarming causes alarm.  
If bell is used as external sounder, fire alarm is pulsed ring; burglary/audible emergency is steady ring.  
Notes: BAT displayed (with no beeping or zone number) indicates system main battery is weak see “Check” and  
“Battery” Displays under TROUBLE CONDITIONS  
• Also see Power Failure, and Other Displays under TROUBLE CONDITIONS.  
34  
 
Protection Zones List  
One or more sensing devices will have been assigned by the installer of your alarm  
system to each of the various protection zones in your system (although not every  
zone number can be used). For example, the sensing device on your Entry/Exit door  
may have been assigned to zone 06, sensing devices on windows in the master  
bedroom to zone 10, and so on.  
Zone numbers 07, 95 and 96 represent Keypad "Panic" alarm functions assigned by  
the installer (see Page 23). Zone numbers 08 and 09 are reserved for Duress and  
Tamper signal reporting to the central station.  
This chart may be used to record the specific zone number assignments for your  
system. Your installer will assist you in recording this information.  
PROTECTION ZONE DESCRIPTIONS  
Zone  
01  
Description  
02  
03  
04  
05  
06  
07  
08  
Key B (or: 6 & #) Panic  
–Duress–  
95  
96  
Key A (or 1 & 6) Panic  
Key C (or 3 & #) Panic  
– 35 –  
 
OWNER'S INSURANCE PREMIUM  
CREDIT REQUEST  
This form should be completed and forwarded to your homeowner's insurance carrier for possible  
premium credit.  
A. GENERAL INFORMATION:  
Insured's Name and Address:___________________________________________________________  
____________________________________________________________  
Insurance Company:  
Policy No.: ________________________  
ADEMCO 4110XM  
Type of Alarm:  
Burglary  
Fire  
Both  
Installed by: _______________________________Serviced by: _______________________________  
Name  
Name  
___________________________________  
_______________________________  
Address  
Address  
B. NOTIFIES (Insert B for Burglary, F for Fire, where appropriate):  
Local Sounding Device ______ Police Dept. ________ Fire Dept. _______  
Central Station ______  
Name __________________________________________________  
Address ________________________________________________  
Phone __________________________________________________  
C. POWERED BY: A.C. With Rechargeable Power Supply  
D. TESTING: Quarterly, Monthly, Weekly,  
Other _______________________  
(continued on other side)  
36  
 
OWNER'S INSURANCE PREMIUM  
CREDIT REQUEST (cont.)  
E. SMOKE DETECTOR LOCATIONS:  
Furnace Room  
Basement  
Kitchen  
Bedrooms  
Attic  
Hall  
Living Room  
Dining Room  
F. BURGLARY DETECTING DEVICE LOCATIONS:  
Front Door  
Basement Door  
All windows  
Rear Door  
All Exterior Doors  
1st Floor Windows  
Interior Locations  
All Accessible Openings, Including Skylights, Air Conditioners and Vents  
G. ADDITIONAL PERTINENT INFORMATION:  
______________________________________________________________________________________  
______________________________________________________________________________________  
______________________________________________________________________________________  
______________________________________________________________________________________  
Signature:_________________________________________________ Date:_____________________  
– 37 –  
 
Regulatory Statements and Warnings  
FEDERAL COMMUNICATIONS COMMISSION STATEMENTS  
The user shall not make any changes or modifications to the equipment unless  
authorized by the Installation Instructions or User's Manual. Unauthorized changes or  
modifications could void the user's authority to operate the equipment.  
CLASS B DIGITAL DEVICE STATEMENT  
This equipment has been tested to FCC requirements and has been found acceptable  
for use. The FCC requires the following statement for your information:  
This equipment generates and uses radio frequency energy and if not installed and  
used properly, that is, in strict accordance with the manufacturer's instructions, may  
cause interference to radio and television reception. It has been type tested and found  
to comply with the limits for a Class B computing device in accordance with the  
specifications in Part 15 of FCC Rules, which are designed to provide reasonable  
protection against such interference in a residential installation. However, there is no  
guarantee that interference will not occur in a particular installation. If this equipment  
does cause interference to radio or television reception, which can be determined by  
turning the equipment off and on, the user is encouraged to try to correct the  
interference by one or more of the following measures:  
• If using an indoor antenna, have a quality outdoor antenna installed.  
• Reorient the receiving antenna until interference is reduced or eliminated.  
• Move the radio or television receiver away from the receiver/control.  
• Move the antenna leads away from any wire runs to the receiver/control.  
• Plug the receiver/control into a different outlet so that it and the radio or television  
receiver are on different branch circuits.  
• Consult the dealer or an experienced radio/TV technician for help.  
FCC / IC STATEMENT  
This device complies with Part 15 of the FCC Rules. Operation is subject to the  
following two conditions: (1) This device may not cause harmful interference, and (2)  
This device must accept any interference received, including interference that may  
cause undesired operation.  
38  
 
Regulatory Statements and Warnings (cont’d)  
TELEPHONE/MODEM INTERFACE  
FCC Part 68  
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that  
contains the FCC registration number and Ringer Equivalence Number (REN). You must provide this information  
to the telephone company when requested.  
This equipment uses the following USOC jack: RJ31X  
This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject  
to state tariffs. This equipment is hearing-aid compatible.  
Ringer Equivalence Number Notice:  
The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the  
maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface  
may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence  
Numbers of all the devices does not exceed 5.  
– 39 –  
 
IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS  
If your security system has been connected to the telephone line, and there is trouble with regular  
telephone service, disconnect the security system from the telephone line by removing the plug from  
the RJ31X (CA38A in Canada) telephone wall jack (you should have been shown how to do this by your  
installing company). Do not attempt to disconnect the telephone line connection inside the control  
cabinet. Doing so will result in the COMPLETE disruption of your regular telephone service.  
If the regular phone works correctly after the plug has been disconnected from the RJ31X wall jack,  
the security system has a problem and you should call your service representative for service  
immediately. If, upon disconnection of the security system from the wall jack, there is still a problem  
with telephone service, notify the telephone company that they have a problem and request prompt  
repair service.  
IMPORTANT: A security system connected to an alarm monitoring station relies on that  
connection.  
• If the security system is at fault, reinsert the plug as soon as the security system is repaired.  
• If the phone service is at fault, re-insert the plug immediately, to ensure resumption of full protection  
upon restoration of phone service.  
The user may not, under any circumstances (in or out of warranty), attempt any service or repairs to  
the system.  
40  
 
Limitations of this System  
WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM  
While this system is an advanced design security system, it does not offer guaranteed protection against burglary or fire or  
other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a  
variety of reasons. For example:  
• Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor  
or disconnect an alarm warning device.  
• Intrusion detectors (e.g. passive infrared detectors), smoke detectors, and many other sensing devices will not work  
without power. Battery operated devices will not work without batteries, with dead batteries, or if the batteries are not  
put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however  
briefly.  
• A user may not be able to reach a panic or emergency button quickly enough.  
• While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not  
activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by  
the Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System  
may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may  
not sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other  
side of closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor  
detector, for example, may not sense a first floor or basement fire. Moreover, smoke detectors have sensing limitations.  
No smoke detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused  
by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable  
materials, overloaded electrical circuits, children playing with matches, or arson. Depending upon the nature of the fire  
and/or the locations of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient  
warning to allow all occupants to escape in time to prevent injury or death.  
• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their  
installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple  
beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot  
detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or  
windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of  
the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however,  
as the ambient temperature of protected area approaches the temperature range of 90° to 105°F (32° to 40°C), the  
detection performance can decrease.  
Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the  
other side of closed or partly open doors. If warning devices sound on a different level of the residence from the  
bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not  
hear the warning if the alarm is muffled from a stereo, radio, air conditioner or other appliance, or by passing traffic.  
Finally, alarm warning devices, however loud, may not warn hearing-impaired people or waken deep sleepers.  
• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service  
or temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.  
• Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect  
themselves from the situation. In the case of a monitored alarm system, authorities may not respond appropriately.  
• This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to  
last as long as 10 years, the electronic components could fail at any time.  
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance.  
This alarm system should be tested weekly to make sure all sensors and transmitters are working properly.  
Installing an alarm system may make one eligible for lower insurance rates, but an alarm system is not a substitute for  
insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and  
continue to insure their lives and property.  
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved  
ones to learn about these developments.  
– 41 –  
 
SERVICING INFORMATION  
Your local authorized service representative is the person best qualified to service  
your alarm system. Arranging a regular program with that person is advisable. Your  
local service representative is:  
NAME: _____________________________________________________________________________  
ADDRESS: _________________________________________________________________________  
PHONE:  
42  
 
TWO YEAR LIMITED WARRANTY  
Honeywell International Inc., acting through its Security & Communications business (“Seller”), 2 Corporate Center Drive,  
Melville, New York 11747 warrants its products to be free from defects in materials and workmanship under normal use and  
service, normal wear and tear excepted, for 24 months from the manufacture date code; provided, however, that in the event the  
Buyer presents a proper invoice relating to the purchased product and such invoice bears a date later than the manufacture  
date, then Seller may at its discretion, reflect the warranty period as commencing at invoice date. Except as required by law, this  
Limited Warranty is only made to Buyer and may not be transferred to any third party. During the applicable warranty period,  
Seller will repair or replace, at its sole option and as the exclusive remedy hereunder, free of charge, any defective products.  
Seller shall have no obligation under this Limited Warranty or otherwise if the product:  
(i)  
is improperly installed, applied or maintained;  
(ii)  
installed outside of stated operating parameters, altered or improperly serviced or repaired by anyone other than  
the Seller/Seller’s Authorized Service/Repair Center;  
(iii)  
(iv)  
damage is caused by outside natural occurrences, such as lightning, power surges, fire, floods, acts of nature, or  
the like; or  
defects result from unauthorized modification, misuse, vandalism, alterations of serial numbers, other causes  
unrelated to defective materials or workmanship, or failures related to batteries of any type used in connection with  
the products sold hereunder.  
Exceptions to Warranty With Respect to Honeywell Products listed below:  
Hardwire Contacts and PIRs – Seller warrants parts for hardwire contacts and PIRs in accordance with the terms of the above  
limited warranty for a period of five (5) years from the manufacture date code.  
EXCLUSION OF WARRANTIES, LIMITATION OF LIABILITY  
THERE ARE NO WARRANTIES OR CONDITIONS, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A  
PARTICULAR PURPOSE OR OTHERWISE, WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. TO THE  
FULLEST EXTENT PERMITTED BY LAW, IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY (i) CONSEQUENTIAL,  
INCIDENTAL, INDIRECT, SPECIAL, OR PUNITIVE DAMAGES ARISING OUT OF OR RELATING IN ANY WAY TO THE PRODUCT  
AND/OR FOR BREACH OF THIS OR ANY OTHER WARRANTY OR CONDITION, EXPRESS OR IMPLIED, OR UPON ANY OTHER  
BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY SELLER’S OWN NEGLIGENCE OR  
FAULT AND EVEN IF SELLER HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH LOSSES OR DAMAGES. Any product  
description (whether in writing or made orally by Seller or Seller’s agents), specifications, samples, models, bulletin, drawings,  
diagrams, engineering sheets or similar materials used in connection with the Buyer’s order are for the sole purpose of  
identifying the Seller’s products and shall not be construed as an express warranty or condition. Any suggestions by Seller or  
Seller’s agents regarding use, applications, or suitability of the products shall not be construed as an express warranty or  
condition unless confirmed to be such in writing by Seller. Seller does not represent that the products it sells may not be  
compromised or circumvented; that the products will prevent any personal injury or property loss by burglary, robbery, fire or  
otherwise, or that the products will in all cases provide adequate warning or protection. Buyer understands that a properly  
installed and maintained alarm may only reduce the risk of a burglary, robbery or fire without warning, but it is not insurance or a  
guarantee that such will not occur or will not cause or lead to personal injury or property loss. CONSEQUENTLY, SELLER  
SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON ANY CLAIM AT  
ALL INCLUDING A CLAIM THE PRODUCT FAILED TO GIVE WARNING. However, if Seller is held liable whether directly or  
indirectly for any loss or damage with respect to the products it sells, regardless of cause or origin, its maximum liability shall not  
in any case exceed the purchase price of the product, which shall be fixed as liquidated damages and not as a penalty, and shall  
be the complete and exclusive remedy against the Seller. Should your product become defective during the warranty, please  
contact your installer to facilitate repair or replacement with Seller pursuant to the terms hereof. Seller reserves the right to  
replace any defective product under warranty with new, refurbished, or remanufactured product.  
– 43 –  
 
– Notes –  
44  
 
– Notes –  
– 45 –  
 
– Notes –  
46  
 
– Notes –  
– 47 –  
 
2 Corporatee Center Drive, Suite 100  
P.O. Box 9040, Melville, NY 11747  
ÊN5100V5BŠ  
N5100V5 4/99 Rev C  
Copyright © 1996 Honeywell International Inc.  
 

Haier Sander HRF 339DVC User Manual
Haier Washer HNS1000TVE ME User Manual
Hamilton Watch Watch Khaki Field Multi Touch User Manual
HANNspree Flat Panel Television LT0G 15U1 000 User Manual
Healthrider Treadmill 831297820 S User Manual
Hotpoint Dishwasher DWF50 User Manual
HP Hewlett Packard Portable Media Storage ESL9322S2 User Manual
Hunter Fan Universal Remote 81002 User Manual
Ice O Matic Ice Maker KE2106 User Manual
Ikelite Digital Camera IXUS 980 IS User Manual