DRAWING DETAILS
PART NUMBER
ISS
ECO AND DATE
0024168 08/06
42011076-003 R2
ARTWORK DESCRIPTION
DRAWN MKTING DATE
CM900 RF INSTALLATION GUIDE (UK - English)
MF
BM
08/06
SIZE AND FOLDING
A3
A4
A5
A6
A7
OTHER
SIZE WHEN PRINTED
SIZE WHEN FOLDED
x
BOOKLET
x
MATERIAL
CARTRIDGE
MATT ART
x
WEIGHT 70g
80g 100g 115g 150g OTHER
x
PRINTING
ONE COLOUR
TWO COLOUR THREE COLOUR FULL COLOUR
SINGLE SIDE
DOUBLE SIDE
x BLACK
x
SEE FOLLOWING PAGES FOR COLOUR DESIGNATION. ALL PRINTING MUST BE
CLEAR, FREE OF SMUDGES AND MULTI COLOUR PRINT PROPERLY REGISTERED
SPECIAL INSTRUCTIONS
Folding Sequence
Finished Size
148mm
CM900 RF
Installation Guide
105mm
xxxxxxxxxx
Part Number
Front
Back
12 page A5 saddle stitched booklet
folded to A6
DO NOT INCLUDE THIS PAGE IN THE PRINTING
CM900 Wireless
Installation Guide
CM927 / CM921 Wireless Programmable
Room Thermostat & HC60NG Receiver Box
Description
Table of Contents
Section
The Honeywell CM900 Wireless (CM927 or
Page
CM921) is
a
modern wireless programmable
1) Installation Information ................................. 2
room thermostat based on Honeywell’s proven
programming philosophy. To further improve the
ease of use, this product includes an extra large
LCD display with backlighting and LoT Technology
to assist customers during daily use.
2) Installing the CM900 Wireless System......... 3
2.1 Installing the Receiver Box .............................. 3
2.2 Installing the Room Thermostat ........................ 4
2.2.1 Power Up............................................... 4
2.2.2 RF Communication Check........................ 4
2.2.3 Locating the Room Thermostat ................. 5
2.3 System Check................................................ 5
The CM927/921 room thermostat communicates
with the HC60NG receiver box on an 868MHz Radio
Frequency (RF) band to control a single heating
system component such as a boiler, pump or
zone valve. Neither product will communicate with
other RF products that use different frequencies or
communication protocols.
3) Basic Operation of the System..................... 6
3.1 Automatic Operation....................................... 6
3.2 Temporary Manual Override............................. 6
3.3 Communication Loss ...................................... 6
Note: The RF link between the individual
room thermostat (CM927/921) and receiver
box (HC60NG) in system packs provided by
Honeywell is pre-configured at the factory and
therefore SHOULD be installed at the same site.
This makes the installation process fast and easy,
but if products from individual system packs are
separated, or mixed with other pre-configured
system packs during installations please refer to
section 5.1 Binding / Rebinding Procedure to
bind the desired units together and allow them to
communicate with each other.
4) Installer Mode................................................. 6
4.1 Entering Installer Mode ................................... 7
4.2 HC60NG Receiver Box Fail-Safe Mode Setup .... 7
4.3 Using the Room Thermostat for Specific Applications .. 8
4.4 Using the Special Features of the Room Thermostat.. 8
4.5 Installer Parameters Table ............................... 9
4.5.1 Category 1 - Room Thermostat Settings ..... 9
4.5.2 Category 2 - System Settings.................. 10
5) Additional Installation Information............. 11
5.1 Binding / Rebinding Procedure ...................... 11
5.2 Multi-Zone System........................................ 11
6) Trouble Shooting.......................................... 12
6.1 Trouble Shooting Guide................................. 12
6.2 Diagnostics Mode ........................................ 12
42011076-003 R2
1) Installation Information
As these products communicate using RF technology special care must be taken during installation. The
location of the RF components as well as the building structure may influence performance of the RF
system. To assure system reliability, please review and apply the information given below.
Within a typical residential building the two products should communicate reliably within a 30m range. It
is important to take into consideration that walls and ceilings will reduce the RF signal. The strength of the
RF signal reaching the receiver box depends on the number of walls and ceilings separating it from the
room thermostat, as well as the building construction - the diagram below illustrates an example of typical
signal strength reduction. Walls and ceilings reinforced with steel or plasterboard walls lined with metal foil
reduce the RF signal significantly more.
Once a position is selected for the room thermostat this can be checked using the RF Communication
Test mode as described in section 2.2.3 Locating the Room Thermostat. If the position is unsuitable the
receiver box will not respond and an alternative position must be selected.
= Signal Strength
Wall
Wall
Wall
Ceiling
Max. Signal Length 30 metres
Typical example of Building Fabric Signal losses
ꢀ
CM900 Wireless - Programmable Room Thermostat
2) Installing the CM900 Wireless System
Please follow the illustrations and information below in sequence to install the receiver box and room
thermostat correctly. For applications other than gas boilers, enabling special features and to see what
other system options are available refer to section 4) Installer Mode.
2.1 Installing the Receiver Box
1
2
3
The receiver box is a RF device. For
the best performance install in an
open space. Leave at least 30cm
distance from any metal objects
including wall boxes and boiler
housing.
NOTE: The receiver box contains no user serviceable parts. It should be
opened and installed by qualified installer only.
Do not mount on metal wall
boxes.
WARNING: Electrostatic sensitive device! Do not touch the circuit board.
4
5
a.
b.
a. Burner (direct control)
b. Combi boiler
> 7mm Ø
< 7mm Ø
c. Zone valve
d. Cooling device
6
7
NOTE: All wiring must be in accordance with IEE
regulations
1.5-2.5mm²
CAuTION: Observe ambient temperature and current
limits (see the receiver box wiring label)
6mm max.
Installation Guide
ꢁ
2.2 Installing the Room Thermostat
2.2.1 Power Up
1. Remove the battery cover and insert the batteries supplied with the room thermostat (2 x AA LR6
Alkaline Batteries).
2. On the initial power up the available user interface languages will be displayed (only on certain models).
Use the
green
or buttons to cycle through the options until the desired language is displayed. Press the
button to confirm the selection.
3. Set the slider switch to the DATE mode.
4. Use the
confirm.
or
or buttons to set the correct time, pressing the green
Install the batteries (included) and attach the instruction label to flap
buttons to set the correct day / month / year, pressing the green
button to
5. Use the
button to confirm.
2.2.2 RF Communication Check (Test Mode)
To check the RF communication, hold the room thermostat about 2-3 metres from the installed receiver
box. Move the slider on the room thermostat to the OFF position then press the and buttons together
with the button for 3 seconds. The unit will display ‘TEST TRANSMIT’ and it will send test signals to the
receiver box, flashing the green LED on every 6 seconds (relay output will remain off) for a maximum of 10
minutes. When the green LED flashes on every 6 seconds proceed to the next step.
NOTE: If the green LED is not switched at specified intervals, the red LED is flashing or if you are installing
a replacement receiver box or room thermostat, follow the procedures described in section 5.1 Binding
/ Rebinding Procedure.
ꢂ
CM900 Wireless - Programmable Room Thermostat
2.2.3 Locating the Room Thermostat
While still in the Test Mode, as described in section 2.2.2, the room thermostat should be located taking
the following into consideration and reviewing the illustrations below:
1. Find a suitable location where the signal transmission is reliable. Reliable transmission is indicated when
the receiver box is flashing the green LED every 6 seconds. NOTE: The receiver box relay will be off.
2. Install the room thermostat EITHER on the wall using the wall bracket OR attach the optional table stand
as shown in below.
3. Exit the Test Mode by moving the setting slider to the required operating mode (AuTO or OFF).
Wall bracket
Table stand
• The room thermostat should be installed in an open space for best performance as it is a radio frequency device.
•
Leave at least 30cm distance from any metal objects including wall boxes and at least 1 metre from any other
electrical equipment eg. radio, TV, PC etc.
• Do not mount onto metal wall boxes. • It is recommended that the receiver box is fully installed.
2.3 System Check
Now a simple test can be completed to check the full system has been installed correctly:
1. Set the slider switch to the OFF mode.
2. Check the boiler supply is on and check that the green LED on the receiver box is off.
3. Set the slider switch to the MAN mode.
4. Adjust the setpoint up to the maximum (35°C) by pressing the
(green LED ON on receiver box) after a few seconds and the symbol appears on the room thermostat
LCD display.
button. The boiler should come on
5. Set the slider switch to the OFF mode. The boiler will go off (green LED OFF on receiver box) after a
few seconds and the symbol disappears.
6. Check the system operation by moving the slider between MAN and OFF modes several times, bearing
in mind the switching delay referred to above.
Now, you should have completed the installation successfully - to begin operating at the default factory
settings move the slider to the AuTO mode or select PROG to modify the built-in heating program
accordingly.
Installation Guide
ꢃ
3) Basic Operation of the System
3.1 Automatic Operation
HC60NG Receiver Box
The receiver box receives the heat demand (0-
100%) signal from the room thermostat. The
room thermostat will display the
symbol on the
LCD display whenever more heat is required.
Depending on the demand the receiver box will
switch the heating device on to match the current
requirements of the system.
Push button and
relay status LED’s
The green LED indicates the status of the relay
output:
• Green LED on = relay on
• Green LED off = relay off
3.2 Temporary Manual Override
Pressing the receiver box button will override the current relay position. As soon as the next signal is
received from the room thermostat the receiver box will return back to automatic operation as the automatic
control has higher priority than manual operation.
3.3 Communications Loss
If the RF communication is lost for a period of 1 hour the red LED will illuminate to indicate that no RF
messages have been received during the last hour.
The receiver box will also enter the failsafe mode as selected in Installer Mode (see section 4.2 HC60
Receiver Box Fail-Safe Mode Setup). To allow manual control of the receiver box output manual override
is available in fail-safe mode. When RF communication is restored the receiver box will automatically return
to normal operation.
You can now use the USER GUIDE supplied with the room thermostat to demonstrate how it works to the
home owner.
4) Installer Mode
Installer Mode is used to alter the system settings for specific applications, to use the special features of
the room thermostat in a different way or to alter the factory preset parameters. Parameters are divided
into two groups:
- Category 1 parameters – Room Thermostat Setup
- Category 2 parameters – System Setup.
These are all listed in section 4.5 Installer Parameters Table.
ꢄ
CM900 Wireless - Programmable Room Thermostat
4.1 Entering Installer Mode
1
2
DAY
COPY
DAY
DATE
PROG
OFF
AUTO
MAN
OFF
CM9ꢀꢅ
The unit will display the first parameter of installer
parameter group category 1 (from Parameter n.1
to n.19) as shown
Move the slider switch to the OFF mode.
Press and hold the button and the two
buttons together.
&
3
4
Press the
change factory setting.
or
to
Press the green
button to confirm the
change.
The display will flash
indicating that a change
has been made.
The display will stop
flashing.
5
6
7
Press
button to go to Installer parameter group
Press
to the next parameter.
button to go
category 2 ( ) (from Parameter n.1 to n.14).
To exit the installer mode, move the slider switch to
the AuTO or MAN positions.
4.2 HC60NG Receiver Box Fail-Safe Mode Setup
The failsafe mode defines the receiver box output relay status if the RF communication is lost (e.g. when
the room thermostat stops communicating due to discharged batteries). The factory setting keeps the
relay permanently off when communications is lost. If this factory setting needs to be changed follow the
instructions below:
1. Enter Installer mode as described above.
2. Press the
button to enter category 2 parameters.
3. Select the parameter 7:LC by pressing the
4. Select the fail-safe mode by pressing
button.
or buttons:
•
•
0 - when RF communication is lost the relay will be held in OFF position.
1 - when RF communication is lost the relay output will cycle at 20% on 80% off.
button to accept the change.
5. Press the green
6. Attach appropriate label to the receiver box to indicate the selected fail-safe mode.
IMPORTANT: To enable the frost protection when RF communication is lost, select the fail-safe mode 1. For
systems with separate frost protection thermostat or where frost protection is not required select fail-safe
mode 0.
Installation Guide
ꢅ
4.3 Using the Room Thermostat for Specific Applications
The CM927/921 RF room thermostat is a versatile controller that can be used to control many different
applications. For most typical applications, like wall-hung gas fired combination boiler control or zone
valve control, no adjustments from the factory settings are required. For other applications, like controlling
an oil burner, the best system performance can be achieved by modifying selected parameters of the
room thermostat in the Installer mode. The table below lists the most common settings used for specific
applications.
Specific Application:
Setting:
What to change:
Cycle/
Hour
Minimum ON Note: All parameters listed below belong to category 2
Time
- System Parameters (see Installer Parameters Table)
HEATING
Gas Boiler (<30kW)
Oil Boiler
6
3
1
4
No changes required
Set 1:Ot parameter to 4
Set 2:Cr parameter to 3
Thermal Actuator
Zone Valve
12
6
1
1
1
Set 2:Cr parameter to 12
No changes required
Electric Heating
(resistive load <8A)
12
Set 2:Cr parameter to 12
Set 3:EH parameter to 1
AIR-
CONDITIONING
To enable switching between cooling and heating
modes adjust parameter 4:HC in category 2 (0 =
disabled, 1 = enabled). Now you can switch between
these modes by pressing the
and
buttons
together for 5 seconds in any of the product operating
modes (AuTO, MAN or OFF). Explain to the end user
how to switch between these modes using the
buttons and ensure the cooling program is modified
as required.
and
Heat Pump / Air-
Conditioner
3
6
4
1
Set 1:Ot parameter to 4
Set 2:Cr parameter to 3
Fan Coil
No changes required
4.4 Using the Special Features of the Room Thermostat
Special Feature:
Description:
Enable/Disable
Optimisation
(Variable Start
Time)
The thermostat will adjust the start time in the morning/afternoon so the
desired temperature is reached by the start of the program period. The
system will restrict the start time to a max of 2 hours.
To enable: Set parameter 8:
OP (category 1) to 1.
Heating or Cooling
Operation
This product can be used for heating or cooling applications. If you select
cooling mode the control algorithm and factory default program will be
modified. You can independently modify the heating and cooling profile.
To enable: Set parameter 4:
HC (category 2) to 1.
Summer/Winter
Auto time change
This feature moves time automatically on the last Sunday of March and
the last Sunday of October. The feature is factory enabled.
To enable: Set parameter 3:
tC (category 1) to 1.
Temperature Offset
If the thermostat is located in a particularly hot/cold location for reliable
signal transmission reasons then the measured/displayed temperature
can be adjusted by +/- 3°C. This is useful if the homeowner wants the
reading to match another appliance temperature display.
Set parameter 12:tO
(category 1) to the required
offset value.
Upper/Lower
Temperature Limit
The normal upper temperature limit of 35°C can be reduced to 21°C
to save the homeowner energy. The normal lower limit of 5°C can be
increased up to 21°C to protect inhabitants from cold.
Set parameter 6:uL (category
1) to the desired upper limit.
Set parameter 7:LL (category
1) to the desired lower limit.
ꢆ
CM900 Wireless - Programmable Room Thermostat
4.5 Installer Parameters Table
4.5.1 Category 1 - Room Thermostat Settings
Parameter
Parameter Factory Default Setting
No.
Optional Setting
Category 1 Parameters – Room Thermostat Settings
Display Description
24 24 hr clock display
Display Description
AM-PM / 24hr
Display
1:CL
2:rP
12
12 hr – AM/PM clock display format
format
Reset Time/ Temp
Program
1
Time / Temp profile set
to factory default
0
Time / Temperature are as programmed
To restore the factory profile set to 1
Changes to 0 when
one of the time/temp
profiles are changed
Auto Summer/
Winter Time
Change
3:tC
1
Auto Summer/Winter
Time Change Enabled
0
0
Auto Summer/Winter Time Change
Disabled
LCD Backlighting
Upper Temp Limit
5:bL
6:uL
1
Backlighting Enable
Backlighting Disabled
35
35°C Upper Temp.
Limit
21 to
34
21°C to 34°C adjustment in 1°C steps
Lower Temp Limit
Optimisation
7:LL
8:OP
12:tO
5
0
0
5°C Lower Temp. Limit 5 to 21 6°C to 21°C adjustment in 1°C steps
Optimisation Disabled
No temperature offset
1
Optimisation Enabled
Temperature Offset
-3 to
+3
-3°C to +3°C adjustment in 0.1°C steps
Proportional Band
Width
13:Pb
19:FS
1.5
1
Proportional band of
1.5 degrees
1.6 to
3.0
1.6°C to 3.0°C adjustment in 0.1°C steps
Settings are as modified above
Reset Parameters
to Factory Defaults
All settings at factory
defaults
0
Changes to 0 when
one of the parameter
is changed
To restore the factory profile set to 1
Notes
1) Remember to always press the green
button to confirm that you want to store your new Installer Set-
Up setting. To exit the Installer Mode move the slider switch to the AuTO or MAN position.
Installation Guide
9
4.5.2 Category 2 - System Settings
Parameter
Parameter Factory Default Setting
No.
Optional Setting
Category 2 Parameters – System Settings (press the
Display Description
1 minute minimum
button to access this category)
Display Description
Minimum boiler
ON time
1:Ot
2:Cr
1
2 to 5
Selection of 2, 3, 4 or 5 minutes
ON time
minimum ON time
Cycle Rate
6
6 cycles per hour
(cph)
3,9 or
12
Selection of 3, 9 or 12 cph
Heat/Cool Change
Pump Exercise
4:HC
5:PE
0
0
Disabled
1
1
Enabled
Pump exercise
disabled
Pump exercise enabled
System
Synchronisation
6:Sn
7:LC
0
0
Standard operation of
the Room Unit
1
1
Room unit configured as Synchroniser
Relay 20% on / 80% off
Loss of
Relay Off
Communications
Instruction
The following Parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating
controls and Wireless Radiator controls. For more information please contact Honeywell sales.
Room Temperature
Sensor Use
8:Su
0
HC60 control
1,2,3
or 4
1 - HR80/HM80 control with own/remote
sensor (no temperature displayed)
2 - Hr80/HM80/HCE80 control with CM
sensor
3 - HC60 control and HR80/HM80/
HCE80 control with own/remote sensor
4 – Hr80/HM80/HCE80 control with own/
remote sensor (temperature displayed)
HR80 Window-
Open Function
9:HO
10:HL
11:uF
12:LF
13:Ar
14:Pr
0
1
Disabled
Enabled
1
0
Enabled
HR80 Local
Override
Disabled
Maximum Flow
Setpoint
55
15
150
15
55°C Maximum Flow
Temp.
0 to 99 0°C to 99°C adjustment in 1°C steps
0 to 50 0°C to 50°C adjustment in 1°C steps
Minimum Flow
Setpoint
15°C Minimum Flow
Temp.
Mixing Value Run
Time
150 seconds
0 to
240
0 to 240 sec. adjustment in 1sec steps
Pump Overrun Run
Time
15 minutes
0 to 99 0 to 99 mins adjustment in 1min steps
Notes
1) Remember to always press the green
button to confirm that you want to store your new Installer Set-
Up setting. To exit the Installer Mode move the slider switch to the AuTO or MAN position.
2) These parameters are set centrally for the zoning system at the room thermostat configured as the
system synchroniser.
3) Minimum on-time setting applies only to the boiler controller. All receiver box zone controllers will work
with the minimum on-time of 30 seconds.
10
CM900 Wireless - Programmable Room Thermostat
5) Additional Installation Information
5.1 Binding / Rebinding Procedure
The binding operation described below is required if:
• Any of the system components (room thermostat or receiver box) are replaced.
• The receiver box has incorrect or no binding data stored (e.g. when pre-bound system pack components
have been mismatched).
NOTE: During the binding procedure keep approximately 1m distance between the room thermostat and
the receiver box.
To bind/rebind:
1. Press and hold the receiver box push button for 15 seconds to reset any previously stored data. After
15 seconds the red LED will change to flashing 0.1sec on/0.9sec off.
NOTE: After 5 seconds the red LED will start to flash 0.5sec on/0.5sec off, but continue to hold the
button).
2. Release the push button.
3. Press and hold the receiver box push button for 5 seconds to enter the binding mode. The Red LED will
start flashing at 0.5sec on/0.5sec off to confirm the binding mode has been entered.
4. Move the room thermostat slider to the OFF position and press the
and buttons together along
with the
button. The unit will display InSt and ‘CONTROL BINDING’.
5. Press the green
button to send the binding signal out to the receiver box. The red LED is switched off
to confirm successful binding operation. If the red LED still flashes push the button again until binding
is successful.
6. Now go to Section 2) Installing the CM900 Wireless System to setup the system.
5.2 Multi-Zone System
Multiple room thermostats and receiver box sets can also be used to control multi-zone systems and the
CM927/921 room thermostat is compatible with a variety of other Honeywell products including HR80
radiator controllers and HCE80 underfloor heating controllers. If you intend to use it in this way additional
installation and user instructions can be obtain by contacting the address at the end of this guide.
NOTE: Some of the labels supplied with the pack are for use in multizone applications.
Installation Guide
11
6) Trouble Shooting
6.1 Trouble Shooting Guide
Symptom (Fault
Message)
Possible Cause
Remedy
The room thermostat
This is normal operation. The receiver box
cycles the relay on and off for times proportional
to the demand signal (0-100%) from the room
thermostat. The symbol only indicates that the
demand value is greater than 0%.
Using the
button change the
temperature setpoint by a few degrees.
The receiver box should switch the relay
on after a few seconds delay.
displays the symbol but
the receiver box relay does
not switch on.
The receiver box does not
react to setpoint changes
on the room thermostat.
The room thermostat and receiver box are not
bound.
Reset the receiver box by pressing and
holding the push button for 15 seconds.
Then follow the binding / rebinding
procedure as described in section 5)
Additional Installation Information.
After the binding procedure
the red LED is on and the
green one is flashing once
every 3 sec on the receiver
box.
Incorrect or incomplete binding procedure.
Repeat the binding procedure.
Incorrect position of the room thermostat during
binding.
Repeat the binding procedure keeping
approx. 1 m distance between the receiver
box and the room thermostat.
The red LED on the
receiver box is illuminated
(Communication loss)
The receiver box receives no RF messages from
the room thermostat:
RF signal is blocked due to wrong location of the Re-locate the room thermostat following
room thermostat.
instructions in section 2) Installing the
CM900 Wireless System.
Room thermostat batteries are exhausted.
Replace batteries in the room thermostat.
6.2 Diagnostic Mode
The CM927/921 room thermostat has a user accessible mode that provides information useful to a remote
service person and a means of checking whether the boiler is working. To access this move the slider
switch to the OFF position then press and hold the button for 5 seconds. The room thermostat will enter
the user settings mode. Next press and hold the and
buttons together. The room thermostat will hold
the relay on for 5 minutes and the following information can be viewed on the display by pressing the
or buttons. : model ID, date code (WW/YY) & checksum.
Hereby, Honeywell declares that this CM927/CM921 room thermostat and HC60NG receiver box are in
compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC, 73/23EC
and 89/336EC.
“Manufactured for and on behalf of the Environment and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37, Switzerland by its Authorised Representative Honeywell International Inc.”
Honeywell Control Systems Ltd.
Arlington Business Park,
Bracknell, Berkshire
RG12 1EB
Technical Help Desk: 08457 678999
42011076-003 R2
© 2006 Honeywell International Inc.
|