Honeywell Thermostat CT2095 User Manual

Honeywell/20  
Programmable Thermostat  
OWNER’S GUIDE  
Weekday/Weekend (5-day/2-day)  
Programmable Heat and/or Cool  
Low Voltage (20 to 30 Vac)  
Thermostat and Mounting Plate  
Model CT2095  
69- 1385  
 
Contents  
Step 1. Prepare for Installation .....................................................................................................  
Step 2. Remove Old Thermostat ..................................................................................................  
Step 3. Install Batteries ................................................................................................................  
4
6
8
Step 4. Program Thermostat ........................................................................................................ 11  
Step 5. Adjust Fan Operation Switch, As Required ...................................................................... 19  
Step 6. Adjust System On-Time, °F/°C, As Required ................................................................... 19  
Step 7. Mount Thermostat Mounting Plate ................................................................................... 21  
Step 8. Wire Thermostat Terminals .............................................................................................. 23  
Step 9. Mount Thermostat ............................................................................................................ 27  
Step 10. Check Thermostat Operation After Programming and Installing ................................... 28  
Step 11. Set Fan and System Switches ....................................................................................... 30  
Troubleshooting Guide ................................................................................................................. 31  
Limited One-Year Warranty .......................................................................................................... 35  
3
69-1385  
 
Step 1. Prepare for Installation  
Check Table 1 to make sure this thermostat is compatible with your system. If not, return it to the  
retailer. For more information, call Honeywell Consumer Services, 1-800-468-1502, Monday -  
Friday, 7 am to 5:30 pm, Central time.  
Table 1. Compatibility Information.  
System Type  
Compatible with CT2095  
Gas—Standing Pilot  
Gas—Electronic Ignition  
Yes  
Yes  
a,b  
Gas-Fired Boilers  
Gas—Millivolt  
Yes  
No  
a,b  
Oil-Fired Boilers  
Oil-Fired Furnace  
Electric Furnace  
Electric Air Conditioning  
Baseboard Electric (120/240 Line Volt)  
Heat Pumps/Multistage Equipment  
Yes  
Yes  
Yes  
Yes  
No  
No  
Not compatible with any 120/240 volt circuit.  
a
Compatible with Honeywell 2-wire zone valves. Isolating relay required for 3-wire thermostats for zone valves.  
Not compatible with 2-wire White-Rodgers no. 1361 valves.  
Compatible with hot water baseboard systems. Does not work efficiently on steam or gravity systems.  
b
4
69-1385  
 
 
Acquire tools and items as needed (see illustration). Also purchase two AA alkaline batteries; we  
recommend Energizer® batteries.  
CROSS-RECESSED  
SCREWDRIVER  
HAND OR  
POWER DRILL  
WITH 3/16 INCH  
DRILL BIT, IF NEEDED  
TO DRILL HOLES  
IN WALL  
WIRE CUTTER/STRIPPER OR SHARP  
KNIFE, IF NEEDED TO STRIP WIRES  
LEVEL, IF NEEDED TO LEVEL  
M13544  
THERMOSTAT FOR APPEARANCE  
5
69-1385  
 
Loosen screws holding thermostat to  
subbase, wallplate or wall, and lift away.  
Disconnect wires from old thermostat or  
subbase. As you disconnect each wire,  
attach one of the enclosed labels to each old  
terminal designation. If there are only two  
wires, they do not need labeling. If there is  
an extra wire that is not connected to your  
old thermostat, you also do not connect it to  
your new thermostat. Keep the wires from  
falling back into the wall by wrapping them  
around a pencil as shown.  
Step 2. Remove Old Thermostat  
Test to be sure your heating and cooling  
systems are working properly. If either does  
not work, contact your local heating/air  
conditioning dealer. To avoid compressor  
damage, do not operate the cooling system  
when outdoor temperature is below 50°F  
(10°C).  
Turn off power to the system at the furnace,  
or at the fuse/circuit breaker panel.  
Carefully unpack your new thermostat and  
mounting plate, saving package of screws,  
instructions and receipt.  
Remove cover from old thermostat. If it does  
not snap off when pulled firmly from the  
bottom, check for a screw used to lock on  
the cover.  
WIRES THROUGH  
WALL OPENING  
M5136  
6
69-1385  
 
 
those systems so return the product to the  
retailer. If you want information about the  
programmable thermostats that work with your  
system, call Honeywell Consumer Services at  
1-800-468-1502.  
Replacing a Clock Thermostat that has  
C or C1 Clock Terminals?  
If you are replacing a Honeywell Chronotherm®  
Thermostat, you may find one or two wires that  
go to the C or C1 clock terminals on the  
Chronotherm® Thermostat wiring wallplate. Do  
not allow them to touch, or you can damage  
your transformer. Disconnect the wires and  
wrap them separately, using electrical tape. Do  
not wrap them together. Place the wires where  
they do not interfere with the operation of the  
new thermostat. Record the colors and terminal  
designation labels of the remaining wires.  
Three thermostat wires?  
If you have three wires for heating only and can  
operate the fan using the fan On switch, this  
thermostat works with your system. However,  
some hot water (zoned) heating systems have  
three thermostat wires. The thermostat does  
not work without installing an isolating relay on  
these systems. For details, call Honeywell  
Consumer Services at 1-800-468-1502.  
Six or more wires?  
If there are six or more wires (excluding clock  
wires attached to terminals), you probably have  
a variation of a heat pump or multistage  
system. This thermostat is not compatible with  
7
69-1385  
 
Step 3. Install Batteries  
IMPORTANT  
Batteries must be installed for the pro-  
gramming and operation of the ther-  
mostat and heating/cooling system.  
Purchase two AA alkaline batteries; non-  
alkaline batteries do not last as long, and  
can leak, causing damage to the thermostat  
or the wall surface. We recommend  
Energizer® batteries.  
Open the top cover of thermostat to access  
control panel and battery compartment.  
Make sure the thermostat is set to the Off  
position.  
BATTERY  
DOOR COVER  
Use a coin to remove the battery cover.  
REMOVING  
BATTERY  
DOOR  
M12492  
8
69-1385  
 
 
Install the fresh batteries as shown, making  
sure positive and negative terminals are  
oriented correctly.  
After the batteries are completely dead, the  
bAtLo indication disappears, leaving a  
completely blank display.  
Replace the battery cover.  
INSTALL TWO AA ALKALINE  
BATTERIES AS SHOWN  
As the batteries run low, a bAt Lo indicator  
flashes for one to two months before the  
batteries run out completely. Replace the  
batteries as soon as possible after the indicator  
starts flashing. If you do not replace the  
batteries sometime during the flashing bAt Lo,  
the indicator eventually stops flashing. bAt Lo  
then stays on without flashing, indicating the  
thermostat and heating/cooling system have  
stopped working and the batteries are almost  
completely dead.  
M1713  
9
69-1385  
 
Press down on the left ends of batteries to  
remove them. If you insert the new batteries  
within 20 to 30 seconds of removing the old  
ones, you do not need to reprogram the  
thermostat. However, if the display is blank, the  
batteries are dead or incorrectly installed and  
you must reprogram. See Step 4.  
IMPORTANT  
Although the thermostat has a low bat-  
tery indicator, replace the batteries  
once a year to prevent the thermostat  
and heating/cooling system from shut-  
ting down due to lack of battery power.  
As a precaution, when leaving home  
for longer than a month, change bat-  
teries before you leave to prevent the  
system from shutting down due to lack  
of battery power.  
10  
 
69-1385  
WAKE is the time period you want the house  
at a comfortable temperature when you get  
up and while you get ready for work or  
school. (This is a higher temperature during  
heating season and a lower temperature dur-  
ing cooling season.)  
LEAVE is the time period you can set for an  
energy-saving temperature while you are  
away at work or school. (This is a lower tem-  
perature during heating season and a higher  
temperature during cooling season.)  
RETURN is the time period you want the  
house at a comfortable temperature for activ-  
ities before bedtime. (This is a higher tem-  
perature during heating season and a lower  
temperature during cooling season.)  
SLEEP is the time period you can set for an  
energy-saving temperature while you are  
sleeping. (This is a lower temperature during  
the heating season and a higher tem-  
perature during the cooling season.)  
Step 4. Program Thermostat  
After the batteries are installed, the thermostat  
can be easily programmed in your hand before  
it is installed on the wall.  
If you prefer to program the thermostat after it is  
installed on the wall, go to Step 7 and return  
later to this programming section.  
The Personal Programming Chart, Tables 2 and  
3, may be helpful for planning your program  
schedule of time and temperature settings for  
various times of the day.  
Four time periods are available during  
weekdays WAKE, LEAVE, RETURN, and  
SLEEP; view these periods individually on the  
display as you press the Weekday key.  
11  
 
69-1385  
 
Set one schedule for weekdays and another for  
weekends because your requirements are  
usually different for each. Also, during week-  
ends, only the WAKE and SLEEP time periods  
are available.  
If no program is entered for the weekends, the  
thermostat operates on the weekday SLEEP  
program all weekend.  
Before programming, remove the clear plastic  
overlay covering the display.  
Fill in the times and temperatures you desire for  
weekdays and weekends. If you decide not to  
program the thermostat, it automatically con-  
trols heating at 68°F (20°C), and cooling at 78°F  
(26°C), 24 hours a day. Also, you do not need to  
enter a time and temperature program for all  
periods if your schedule does not require it. For  
example, a house that is occupied during week-  
days would require programs only for WAKE  
and SLEEP.  
When pressing the keys, use the ball of your  
finger or a soft pencil eraser. Using sharp finger-  
nails or pencil points can damage the keypad.  
If you make an error at any time during program-  
ming, just press the Run Program key, and  
continue again at the previous step in your  
sequence.  
12  
 
69-1385  
Table 2. Personal Programming Chart for Heating.  
Days of Week Heating Program Start Time Heating Temperature  
a
Weekdays  
WAKE  
LEAVE  
RETURN  
SLEEP  
b
Weekends  
WAKE  
SLEEP  
a
b
The temperatures cannot be set any higher than 88°F (31°C) or any lower than 45°F (7°C).  
If you decide not to enter weekend programs, the thermostat operates on the weekday SLEEP pro-  
gram all weekend.  
13  
 
69-1385  
.
Table 3. Personal Programming Chart for Cooling.  
Days of Week Cooling Program Start Time Cooling Temperature  
a
Weekdays  
WAKE  
LEAVE  
RETURN  
SLEEP  
b
Weekends  
WAKE  
SLEEP  
a
b
The temperatures cannot be set any higher than 88°F (31°C) or any lower than 45°F (7°C).  
If you decide not to enter weekend programs, the thermostat operates on the weekday SLEEP pro-  
gram all weekend.  
14  
 
69-1385  
NOTE: Batteries are required for operation and programming. When inserting batteries, set the  
System switch to Off. Remove the battery door (on the thermostat left side) using a coin at  
the bottom. Follow instructions in Step 3. Also see the label inside the battery cover for  
abbreviated programming procedures for your thermostat.  
Time  
Set Current Time/Day  
Clock/Day  
To set time, press and release  
once, press  
until current shows. To set day, press and  
Time  
Clock/Day  
Run Program  
release  
again, press  
until current day shows; then press  
.
Heating Program  
Weekday  
With System switch at Heat, press and release  
SET appear on display.  
once. WAKE, MON FRI (Monday-Friday), and  
TEMP  
Time  
Use  
toprogram WAKEtimeand  
toprogram WAKE temperatureforMONFRI(Monday-Friday).  
Repeat sequence for LEAVE, RETURN, SLEEP.  
15  
 
69-1385  
Time  
Weekend  
Press  
until SAT SUN (Saturday-Sunday), WAKE and SET appear on display. Use  
to program  
TEMP  
WAKE time and  
to program WAKE temperature for SAT SUN (Saturday-Sunday).  
Run Program  
Repeat sequence for SLEEP. Press and release  
to start the program.  
Cooling Program  
With System switch at Cool, follow the same instructions as for the Heating Program.  
Run Program  
After programming, adjust the Fan and System switches, as desired. Press and release  
start the program.  
to  
16  
 
69-1385  
Operating Your Thermostat  
System switch must be set to Heat or Cool to perform the following:  
TEMP  
Temporarily Change Temperature for current period only — Press  
; temporary indicator shows  
Run Program  
on display and cancels itself at the next scheduled change; to cancel sooner, press  
.
TEMP  
Hold Temp  
Hold a Temperature Indefinitely (such as when on vacation) Press  
and  
; HOLD  
Run Program  
appears on display; to cancel, press  
.
Present Set  
Check Current Temperature Setting — Press  
.
Weekday  
Weekend  
Check Programs — Press  
,
repeatedly to see each time and temperature; then press  
Run Program  
.
17  
 
69-1385  
Clear  
Weekday  
Weekend  
Cancel Program — Press  
,
until program to cancel shows; then press  
.
Usage  
Check Usage — Press  
to see length of time heat or air conditioning has run today since  
Clear  
midnight; press again for yesterdays usage, press again for cumulative; press  
to clear  
Run Program  
cumulative reading, if desired; then press  
.
Permanently Change a Program — Repeat Heating Program or Cooling Program steps, as  
applicable.  
Run Program  
Return to Normal Program or Start Program Press  
.
18  
 
69-1385  
as a guide. The system on-time should be  
optimized according to the type of system to  
maximize comfort. Setting the screw out one  
turnmeans turning the screw approximately  
360° counterclockwise, or about one com-  
plete turn.  
Step 5. Adjust Fan Operation  
Switch, As Required  
The thermostat fan operation switch, labeled  
FUELSWITCH (see illustration) isfactory-set  
in the F position. This is the correct setting for  
most systems. If your system is an electric  
heat system, set the switch to E to allow the  
fan to turn on immediately with the heating in  
a system when the G terminal is connected.  
THERMOSTAT BACK  
A
B
C
D
ADJUST SCREWS THROUGH HOLES  
TO SELECT OPERATION DESIRED  
DISPLAY °F C–IN  
DISPLAY °C C–OUT  
1 TURN  
FUEL SWITCH  
POSITION  
HEATING SYSTEM  
WARM AIR A–IN  
FURNACE  
HOT WATER A–OUT B–IN  
BOILER 1 TURN  
ELECTRIC A–IN  
FURNACE  
B–IN  
F
F
E
B–OUT  
1 TURN  
Step 6. Adjust System On-Time,  
°F/°C, As Required  
W
Y
G
FOR HIGH EFFICIENCY FURNACE (90%+ AFUE)  
ADJUST: SCREW A–OUT ONE TURN  
SCREW B–IN  
FUEL SWITCH – F POSITION  
FUEL SWITCH  
The thermostat on-time is factory-set for a  
warm air, gas or oil heating system. If you are  
installing it on another type of system, adjust  
the on-time accordingly by setting screws A  
and B on the back of the thermostat. Use the  
heating system table shown in the illustration  
F
E
Rc  
R
M8796A  
19  
 
69-1385  
   
In the unlikely event that you want a longer  
furnace on-time, readjust screws A and/or B as  
follows:  
IMPORTANT  
When using a high efficiency furnace  
such as a 90 percent or greater Aver-  
age Fuel Utilization Efficiency (AFUE)  
unit, adjust screw A out one turn and  
leave screw B in.  
First, turn both screws in completely, then  
adjust for system type:  
Warm Air FurnaceSet at the Hot Water  
setting (Aout one turn, Bleave in).  
Electric FurnaceLeave at the Warm Air  
Furnace setting (Aleave in, Bleave in).  
The thermostat is set to read the temperature  
in degrees Fahrenheit. If readings are  
desired in degrees Celsius, adjust screw C  
out one turn.  
NOTE: This thermostat does not have a set-  
ting for steam/gravity air; cycles would  
not be long enough for accurate tem-  
perature control.  
20  
 
69-1385  
Step 7. Mount Thermostat  
Mounting Plate  
WALL ANCHORS (2)  
WIRES THROUGH  
WALL OPENING  
Position mounting plate on wall. Use level to  
make sure mounting plate is level. Use a  
pencil to mark the two mounting holes.  
Remove mounting plate from wall, and drill  
3/16-inch holes in wall (if drywall) as marked.  
For firmer material such as plaster or wood,  
drill 7/32-inch holes. Gently tap anchors  
(provided) into drilled holesuntil flush with the  
wall.  
WALL  
MOUNTING  
PLATE  
Reposition mounting plate over holes,  
pulling wires through wiring opening.  
Loosely insert two mounting screws into  
holes.  
MOUNTING  
SCREWS (2)  
M1718  
21  
 
69-1385  
 
Level for appearance only; thermostat  
functions properly even when not level.  
Tighten mounting screws.  
LEVEL  
M1714A  
22  
 
69-1385  
Step 8. Wire Thermostat Terminals  
NOTE: All wiring must comply with local codes  
and ordinances. If unsure about house-  
hold wiring procedures, call your local  
heating/air conditioning contractor.  
WIRE NUT SIZE FOR  
TWO 18-GAUGE WIRES  
METHOD TO INCREASE WIRE LENGTH  
6 IN. (152 MM)  
WIRE  
FROM  
WALL  
Refer to the labels you placed on the terminal  
wireswhenyouremovedyour oldthermostat.  
Match the letter of your old thermostat wire  
with the terminal of the corresponding letter  
on the back of your new thermostat. (See  
wiring diagrams.) Hold the thermostat as  
shown in illustration to minimize need for wire  
extenders. If wires are still too short, use wire  
connectors (purchased locally) to extend  
wires. See illustration for guidelines on using  
wire extenders.  
OF 18-GAUGE  
THERMOSTAT  
WIRE. MATCH  
INSULATION  
COLORS  
OR MARK  
WIRE ENDS.  
M1715A  
In 5-wire installations only, be sure to remove  
the factory-installed jumper connecting termi-  
nals R and Rc.  
23  
 
69-1385  
 
Loosen the terminal screws and slip each wire beneath its matching terminal. See illustrations for  
wire insertion technique.  
Securely tighten terminals.  
Plug the hole in the wall with insulation to help prevent drafts from adversely affecting thermostat  
operation.  
JUMPER (FACTORY-  
INSTALLED). REMOVE  
IF 5-WIRE SYSTEM  
INSERT  
STRAIGHT  
UNDER  
5/16 in.  
(8 mm)  
STRIP  
c
SCREW HEAD  
R
R
END OF WIRE  
VISIBLE HERE  
M1712B  
G
W
Y
M3002A  
24  
 
69-1385  
2-WIRE HEAT-ONLY (JUMPER INTACT)  
4-WIRE HEAT/COOL (JUMPER INTACT)  
A
C
A
C
B
D
B
D
JUMPER  
W
R
Y
G
W
R
Y
G
JUMPER  
Rc  
Rc  
HEATING  
RELAY OR  
VALVE COIL  
COOLING  
CONTACTOR  
COIL  
HEATING  
RELAY OR  
VALVE COIL  
L1  
(HOT)  
1
L2  
FAN  
L1  
(HOT)  
RELAY  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REQUIRED.  
M1709B  
L2  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REQUIRED.  
M1710B  
25  
 
69-1385  
5-WIRE HEAT/COOL (JUMPER REMOVED)  
3-WIRE COOL-ONLY (JUMPER INTACT)  
A
C
A
C
B
D
B
D
W
R
Y
G
W
R
Y
G
JUMPER  
Rc  
Rc  
HEATING  
RELAY OR  
VALVE COIL  
FAN  
RELAY  
COOLING  
CONTACTOR  
COIL  
COOLING  
CONTACTOR  
COIL  
FAN  
RELAY  
1
1
L1  
(HOT)  
L1  
L2  
L1  
(HOT)  
L2  
L2  
1
(HOT)  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REQUIRED.  
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REQUIRED.  
M848A  
M1711C  
26  
 
69-1385  
Step 9. Mount Thermostat  
NOTE: To remove thermostat from wall, first pull out at bottom of thermostat, then remove top.  
SWING OPEN COVER TO  
CHECK OPERATION.  
A. ENGAGE TABS AT TOP OF  
B. PRESS LOWER EDGE  
OF CASE TO LATCH.  
C.  
THERMOSTAT AND SUBBASE.  
AM  
TU  
LE  
AV  
E
Cl  
oc  
k/  
Da  
y
Ti  
m
e
TE  
M
P
Ru  
n
Pr  
ld  
og  
ra  
m
W
ee  
kd  
ay  
Ho  
Te  
m
p
W
ee  
ke  
nd  
Cl  
ea  
r
Us  
ag  
e
Pr  
es  
en  
t
S
et  
Fan  
uto  
A
O
n
S
ys  
te  
m
C
ool  
O
ff  
H
eat  
M13545  
27  
 
69-1385  
 
Move the System switch to  
Heat and the Fan switch to  
Auto.  
Cool  
Off  
Heat  
Step 10. Check Thermostat  
Operation After Programming  
and Installing  
0
Auto  
On  
TEMP  
Heating  
Press TEMP key until the set-  
ting is about 10°F (6°C) above  
room temperature. Heating  
should start and the fan should  
run after a short delay (immedi-  
Do not check heating system operation by  
jumpering thermostat terminals such as gas  
valve, zone valve, and oil burner control at the  
primary control. This damages the thermostat.  
Instead, jumper R and W wires at the  
thermostat.  
ately if fan operation switch is set to E position).  
Press TEMP key until setting is about 10°F (6°C)  
below room temperature. The heating equip-  
ment should shut off.  
28  
 
69-1385  
 
Move the System switch to  
Cool and the Fan switch to  
Auto.  
Cool  
Off  
Heat  
Cooling  
To avoid possible compressor damage, do not  
operate the cooling system when outdoor  
temperature is below 50°F (10°C). See  
compressor manufacturer instructions.  
Auto  
On  
TEMP  
IMPORTANT  
Press TEMP key until setting is  
about 10°F (6°C) below room  
temperature. The cooling  
When cooling setting is changed, ther-  
mostat delays up to five minutes  
before turning on the air conditioner.  
This delay protects the compressor.  
equipment and fan should start.  
Press TEMP key until the setting is about 10°F  
(6°C) above room temperature. The cooling  
equipment and fan should stop.  
Move the System switch to Off;  
Cool  
Off  
Heat  
keep the Fan switch at Auto.  
The system and fan should be  
off.  
Auto  
On  
29  
 
69-1385  
Step 11. Set Fan and System Switches  
First set the Fan switch.  
Then set the System switch.  
Cool: The thermostat controls  
your air conditioning  
system.  
Fan Auto: Normal setting for most  
Auto  
On  
Cool  
Cool  
Cool  
Off  
Off  
Off  
Heat  
Heat  
Heat  
homes. A single-speed fan will  
turn on automatically with the air  
conditioner or furnace. A two-speed fan  
usually runs on high with the air conditioner  
and on low with the furnace.  
Off: Both the heating and air  
conditioning systems are  
off.  
Fan On: The fan runs continuously.  
Auto  
On  
Use for improved air circulation  
during special occasions or for  
more efficient electronic air  
Heat: The thermostat  
controls your heating  
system.  
cleaning. (In a heat-only system, fan runs  
continuously only if fan relay is connected to  
the thermostat.)  
30  
 
69-1385  
 
Troubleshooting Guide  
If...  
Then...  
Display does not come on. Set the System switch to Off. Remove batteries. Insert them backward  
for at least five seconds to reset the thermostat. Replace batteries  
correctly. Display should come on.  
Make sure batteries are fresh and installed correctly.  
Temperature display does You have reached the temperature setting limit. The setting range is  
not go lower than 45°F  
45°F to 88°F (7° to 31°C).  
(7°C) or higher than 88°F  
(31°C) during programming.  
Temperature change occurs Check the program times for the questionable period. Be sure that AM  
at wrong times.  
and PM indications are correct. Make sure the current day and time  
are correct. Reprogram, if necessary.  
31  
 
69-1385  
 
If...  
Heating does not come on. Check that the System switch is set to Heat.  
Make sure the heating setpoint is above the room temperature.  
Then...  
Check the system fuse or circuit breaker and replace or reset, if  
necessary.  
Make sure the System switch is in the On position; set it to On if it is in  
the Off position.  
If temperature setting is higher than the current temperature and the  
display says HEAT, contact Honeywell Consumer Services at 1-800-  
468-1502.  
Cooling does not come on. Check that the System switch is set to Cool.  
Make sure the cooling setpoint is below the room temperature.  
Check the system fuse or circuit breaker and replace or reset, if  
necessary.  
Make sure the System switch at the air conditioner is in the On  
position; set it to On if it is in the Off position.  
32  
 
69-1385  
If...  
Then...  
Cooling does not come on The thermostat has a built-in time delay on cooling. Allow five to ten  
(Continued).  
minutes after changing the setting before the air conditioner starts.  
If temperature setting is lower than current temperature, and the  
display says COOL, move the System switch from Cool to Off for ten  
minutes. After ten minutes, return the switch to the Cool position. If air  
conditioner comes on, compressor may have reached its high-limit  
temperature protection and shut down.If air conditioner does not come  
on after the ten minutes and the display says COOL, contact  
Honeywell Consumer Services at 1-800-468-1502.  
If two- or four-wire installation, verify R-Rc jumper is installed.  
Press Present Set key to check the current temperature setting.  
The house is too warm or  
too cool.  
If desired, change the temperature setting. See Cooling Program  
section.  
SYSTEM ON indicator is  
lighted, but no heat is  
Allow time for the furnace to heat up and the fan to come on before  
checking for heat at the register. (Check to make sure system on-time  
coming from the registers. is set correctly. See Step 6.)  
33  
 
69-1385  
Toll-free Customer Assistance  
For all questions concerning this thermostat, please read and follow the instructions. If additional  
assistance is needed, call Honeywell Consumer Services at 1-800-468-1502, Monday - Friday,  
7:00 a.m. - 5:30 p.m. Central time.  
Before you call, please have the following information availablethermostat model number and  
date code, type of heating/cooling system (hot water, warm air, oil, gas, etc.), and number of wires  
connected to the thermostat.  
NOTICE  
This equipment is a Class B digital apparatus, which complies with Canadian Radio Interference  
Regulations, CRC c.1374.  
34  
 
69-1385  
Limited One-Year Warranty  
Honeywell warrants this product, excluding battery, to be free from defects in the workmanship or materials, under normal use and  
service, for a period of one (1) year from the date of purchase by the consumer. If, at any time during the warranty period, the  
product is defective or malfunctions, Honeywell shall repair or replace it (at Honeywells option) within a reasonable period of time.  
If the product is defective,  
(i) return it, with a bill of sale or other dated proof of purchase, to the retailer from which you purchased it, or  
(ii) package it carefully, along with proof of purchase (including date of purchase) and a short description of the malfunction, and  
mail it, postage prepaid, to the following address:  
Honeywell Inc.  
Canada: Honeywell Limited/Honeywell Limitée  
Product ServicesON15-FFE  
Return Goods Department  
1050 Berkshire Lane  
Plymouth, MN 55441-4437  
740 Ellesmere Road  
Scarborough, Ontario M1P 2V9  
This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by Honeywell that the  
defect or malfunction was caused by damage which occurred while the product was in the possession of a consumer.  
Honeywells sole responsibility shall be to repair or replace the product within the terms stated above. HONEYWELL SHALL NOT  
BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES  
RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY  
OTHER FAILURE OF THIS PRODUCT. Some states do not allow the exclusion or limitation of incidental or consequential  
damages, so this limitation may not apply to you.  
35  
 
69-1385  
 
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY HONEYWELL MAKES ON THIS PRODUCT. THE DURATION OF  
ANY IMPLIED WARRANTIES, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR  
PURPOSE, IS HEREBY LIMITED TO THE ONE YEAR DURATION OF THIS WARRANTY. Some states do not allow limitations  
on how long an implied warranty lasts, so the above limitation may not apply to you.  
This warranty gives you specific legal rights, and you may have other rights which vary from state to state.  
If you have any questions concerning this warranty, please write our Customer Assistance Center, Honeywell Inc., P.O. Box 524,  
Minneapolis, MN 55440-0524 or call 1-800-468-1502, Monday-Friday, 7:00 a.m. to 5:30 p.m., Central time. In Canada, write  
Retail Products ON15-02H, Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 2C9.  
36  
 
69-1385  
TYPICAL ENERGY SAVINGS FOR REPRESENTATIVE CITIES IN THE U.S. AND CANADA  
Savings for Once-A-Day  
10°F (5°C) decrease  
Savings for Twice-A-Day  
10°F (5°C) decrease*  
Savings for 5°F (3°)  
summer increase  
30%  
28%  
26%  
24%  
22%  
20%  
18%  
16%  
14%  
12%  
10%  
8%  
6%  
4%  
2%  
Calgary  
Halifax  
Vancouver Buffalo  
Cleveland  
Milwaukee  
Denver  
Des Moines Chicago  
Boston  
New York  
Louisville  
Portland  
Wash., D C  
San Dallas  
Francisco Atlanta  
Los Angeles San Diego  
Minneapolis Edmonton  
Cincinnati  
Kansas City Philadelphia  
St. Louis  
St. Paul  
Montreal  
Ottawa  
Toronto  
Regina  
Moncton  
North Bay  
Quebec  
Omaha  
Salt Lake  
City  
Detroit  
Pittsburgh  
Indianapolis  
Seattle  
Winnipeg  
Columbus  
St. John's  
*Based on 10°F (5°C) decrease(5°F [3°C] decrease  
gives approximately 55 percent of these savings).  
M2416A  
37  
 
69-1385  
38  
 
69-1385  
39  
 
69-1385  
Home and Building Control  
Honeywell Inc.  
Honeywell Plaza  
Home and Building Control  
Honeywell Limited-Honeywell Limitée  
155 Gordon Baker Road  
North York, Ontario  
P.O. Box 524  
Minneapolis, MN 55408-0524  
M2H 3N7  
Printed in U.S.A. on recycled  
 
paper containing at least 10%  
post-consumer paper fibers.  
69-1385 G.H. 6-00  

Graco Inc Paint Sprayer 130 Convertible User Manual
Graham Field Mobility Aid CKD12F7T User Manual
Groupe SEB USA T FAL Iron FV5210 User Manual
HANNspree Handheld TV ST40 12A1 User Manual
Honeywell Fan HT9700 User Manual
HP Hewlett Packard Personal Computer 384529 001 User Manual
HTC Cell Phone X+ User Manual
Husqvarna Chainsaw 1153178 95 User Manual
IBM Conference Phone 8141 User Manual
IMC Networks Network Card IE IMCV T1 MUX 4 User Manual