Honeywell/20
Programmable Thermostat
OWNER’S GUIDE
Weekday/Weekend (5-day/2-day)
Programmable Heat and/or Cool
Low Voltage (20 to 30 Vac)
Thermostat and Mounting Plate
Model CT2095
Place Bar Code Here
69- 1385
Contents
Step 1. Prepare for Installation .....................................................................................................
Step 2. Remove Old Thermostat ..................................................................................................
Step 3. Install Batteries ................................................................................................................
4
6
8
Step 4. Program Thermostat ........................................................................................................ 11
Step 5. Adjust Fan Operation Switch, As Required ...................................................................... 19
Step 6. Adjust System On-Time, °F/°C, As Required ................................................................... 19
Step 7. Mount Thermostat Mounting Plate ................................................................................... 21
Step 8. Wire Thermostat Terminals .............................................................................................. 23
Step 9. Mount Thermostat ............................................................................................................ 27
Step 10. Check Thermostat Operation After Programming and Installing ................................... 28
Step 11. Set Fan and System Switches ....................................................................................... 30
Troubleshooting Guide ................................................................................................................. 31
Limited One-Year Warranty .......................................................................................................... 35
3
69-1385
Step 1. Prepare for Installation
❑ Check Table 1 to make sure this thermostat is compatible with your system. If not, return it to the
retailer. For more information, call Honeywell Consumer Services, 1-800-468-1502, Monday -
Friday, 7 am to 5:30 pm, Central time.
Table 1. Compatibility Information.
System Type
Compatible with CT2095
Gas—Standing Pilot
Gas—Electronic Ignition
Yes
Yes
a,b
Gas-Fired Boilers
Gas—Millivolt
Yes
No
a,b
Oil-Fired Boilers
Oil-Fired Furnace
Electric Furnace
Electric Air Conditioning
Baseboard Electric (120/240 Line Volt)
Heat Pumps/Multistage Equipment
Yes
Yes
Yes
Yes
No
No
Not compatible with any 120/240 volt circuit.
a
Compatible with Honeywell 2-wire zone valves. Isolating relay required for 3-wire thermostats for zone valves.
Not compatible with 2-wire White-Rodgers no. 1361 valves.
Compatible with hot water baseboard systems. Does not work efficiently on steam or gravity systems.
b
4
69-1385
❑ Acquire tools and items as needed (see illustration). Also purchase two AA alkaline batteries; we
recommend Energizer® batteries.
CROSS-RECESSED
SCREWDRIVER
HAND OR
POWER DRILL
WITH 3/16 INCH
DRILL BIT, IF NEEDED
TO DRILL HOLES
IN WALL
WIRE CUTTER/STRIPPER OR SHARP
KNIFE, IF NEEDED TO STRIP WIRES
LEVEL, IF NEEDED TO LEVEL
M13544
THERMOSTAT FOR APPEARANCE
5
69-1385
❑ Loosen screws holding thermostat to
subbase, wallplate or wall, and lift away.
❑ Disconnect wires from old thermostat or
subbase. As you disconnect each wire,
attach one of the enclosed labels to each old
terminal designation. If there are only two
wires, they do not need labeling. If there is
an extra wire that is not connected to your
old thermostat, you also do not connect it to
your new thermostat. Keep the wires from
falling back into the wall by wrapping them
around a pencil as shown.
Step 2. Remove Old Thermostat
❑ Test to be sure your heating and cooling
systems are working properly. If either does
not work, contact your local heating/air
conditioning dealer. To avoid compressor
damage, do not operate the cooling system
when outdoor temperature is below 50°F
(10°C).
❑ Turn off power to the system at the furnace,
or at the fuse/circuit breaker panel.
❑ Carefully unpack your new thermostat and
mounting plate, saving package of screws,
instructions and receipt.
❑ Remove cover from old thermostat. If it does
not snap off when pulled firmly from the
bottom, check for a screw used to lock on
the cover.
WIRES THROUGH
WALL OPENING
M5136
6
69-1385
those systems so return the product to the
retailer. If you want information about the
programmable thermostats that work with your
system, call Honeywell Consumer Services at
1-800-468-1502.
Replacing a Clock Thermostat that has
C or C1 Clock Terminals?
If you are replacing a Honeywell Chronotherm®
Thermostat, you may find one or two wires that
go to the C or C1 clock terminals on the
Chronotherm® Thermostat wiring wallplate. Do
not allow them to touch, or you can damage
your transformer. Disconnect the wires and
wrap them separately, using electrical tape. Do
not wrap them together. Place the wires where
they do not interfere with the operation of the
new thermostat. Record the colors and terminal
designation labels of the remaining wires.
Three thermostat wires?
If you have three wires for heating only and can
operate the fan using the fan On switch, this
thermostat works with your system. However,
some hot water (zoned) heating systems have
three thermostat wires. The thermostat does
not work without installing an isolating relay on
these systems. For details, call Honeywell
Consumer Services at 1-800-468-1502.
Six or more wires?
If there are six or more wires (excluding clock
wires attached to terminals), you probably have
a variation of a heat pump or multistage
system. This thermostat is not compatible with
7
69-1385
Step 3. Install Batteries
IMPORTANT
Batteries must be installed for the pro-
gramming and operation of the ther-
mostat and heating/cooling system.
❑ Purchase two AA alkaline batteries; non-
alkaline batteries do not last as long, and
can leak, causing damage to the thermostat
or the wall surface. We recommend
Energizer® batteries.
❑ Open the top cover of thermostat to access
control panel and battery compartment.
❑ Make sure the thermostat is set to the Off
position.
BATTERY
DOOR COVER
❑ Use a coin to remove the battery cover.
REMOVING
BATTERY
DOOR
M12492
8
69-1385
❑ Install the fresh batteries as shown, making
sure positive and negative terminals are
oriented correctly.
After the batteries are completely dead, the
bAtLo indication disappears, leaving a
completely blank display.
❑ Replace the battery cover.
INSTALL TWO AA ALKALINE
BATTERIES AS SHOWN
As the batteries run low, a bAt Lo indicator
flashes for one to two months before the
batteries run out completely. Replace the
batteries as soon as possible after the indicator
starts flashing. If you do not replace the
batteries sometime during the flashing bAt Lo,
the indicator eventually stops flashing. bAt Lo
then stays on without flashing, indicating the
thermostat and heating/cooling system have
stopped working and the batteries are almost
completely dead.
M1713
9
69-1385
Press down on the left ends of batteries to
remove them. If you insert the new batteries
within 20 to 30 seconds of removing the old
ones, you do not need to reprogram the
thermostat. However, if the display is blank, the
batteries are dead or incorrectly installed and
you must reprogram. See Step 4.
IMPORTANT
Although the thermostat has a low bat-
tery indicator, replace the batteries
once a year to prevent the thermostat
and heating/cooling system from shut-
ting down due to lack of battery power.
As a precaution, when leaving home
for longer than a month, change bat-
teries before you leave to prevent the
system from shutting down due to lack
of battery power.
10
69-1385
•
WAKE is the time period you want the house
at a comfortable temperature when you get
up and while you get ready for work or
school. (This is a higher temperature during
heating season and a lower temperature dur-
ing cooling season.)
LEAVE is the time period you can set for an
energy-saving temperature while you are
away at work or school. (This is a lower tem-
perature during heating season and a higher
temperature during cooling season.)
RETURN is the time period you want the
house at a comfortable temperature for activ-
ities before bedtime. (This is a higher tem-
perature during heating season and a lower
temperature during cooling season.)
SLEEP is the time period you can set for an
energy-saving temperature while you are
sleeping. (This is a lower temperature during
the heating season and a higher tem-
perature during the cooling season.)
Step 4. Program Thermostat
After the batteries are installed, the thermostat
can be easily programmed in your hand before
it is installed on the wall.
If you prefer to program the thermostat after it is
installed on the wall, go to Step 7 and return
later to this programming section.
•
•
•
The Personal Programming Chart, Tables 2 and
3, may be helpful for planning your program
schedule of time and temperature settings for
various times of the day.
Four time periods are available during
weekdays — WAKE, LEAVE, RETURN, and
SLEEP; view these periods individually on the
display as you press the Weekday key.
11
69-1385
Set one schedule for weekdays and another for
weekends because your requirements are
usually different for each. Also, during week-
ends, only the WAKE and SLEEP time periods
are available.
If no program is entered for the weekends, the
thermostat operates on the weekday SLEEP
program all weekend.
Before programming, remove the clear plastic
overlay covering the display.
Fill in the times and temperatures you desire for
weekdays and weekends. If you decide not to
program the thermostat, it automatically con-
trols heating at 68°F (20°C), and cooling at 78°F
(26°C), 24 hours a day. Also, you do not need to
enter a time and temperature program for all
periods if your schedule does not require it. For
example, a house that is occupied during week-
days would require programs only for WAKE
and SLEEP.
When pressing the keys, use the ball of your
finger or a soft pencil eraser. Using sharp finger-
nails or pencil points can damage the keypad.
If you make an error at any time during program-
ming, just press the Run Program key, and
continue again at the previous step in your
sequence.
12
69-1385
Table 2. Personal Programming Chart for Heating.
Days of Week Heating Program Start Time Heating Temperature
a
Weekdays
WAKE
LEAVE
RETURN
SLEEP
b
Weekends
WAKE
SLEEP
a
b
The temperatures cannot be set any higher than 88°F (31°C) or any lower than 45°F (7°C).
If you decide not to enter weekend programs, the thermostat operates on the weekday SLEEP pro-
gram all weekend.
13
69-1385
.
Table 3. Personal Programming Chart for Cooling.
Days of Week Cooling Program Start Time Cooling Temperature
a
Weekdays
WAKE
LEAVE
RETURN
SLEEP
b
Weekends
WAKE
SLEEP
a
b
The temperatures cannot be set any higher than 88°F (31°C) or any lower than 45°F (7°C).
If you decide not to enter weekend programs, the thermostat operates on the weekday SLEEP pro-
gram all weekend.
14
69-1385
NOTE: Batteries are required for operation and programming. When inserting batteries, set the
System switch to Off. Remove the battery door (on the thermostat left side) using a coin at
the bottom. Follow instructions in Step 3. Also see the label inside the battery cover for
abbreviated programming procedures for your thermostat.
Time
Set Current Time/Day
Clock/Day
To set time, press and release
once, press
until current shows. To set day, press and
Time
Clock/Day
Run Program
release
again, press
until current day shows; then press
.
Heating Program
Weekday
With System switch at Heat, press and release
SET appear on display.
once. WAKE, MON FRI (Monday-Friday), and
TEMP
Time
Use
toprogram WAKEtimeand
toprogram WAKE temperatureforMONFRI(Monday-Friday).
Repeat sequence for LEAVE, RETURN, SLEEP.
15
69-1385
Time
Weekend
Press
until SAT SUN (Saturday-Sunday), WAKE and SET appear on display. Use
to program
TEMP
WAKE time and
to program WAKE temperature for SAT SUN (Saturday-Sunday).
Run Program
Repeat sequence for SLEEP. Press and release
to start the program.
Cooling Program
With System switch at Cool, follow the same instructions as for the Heating Program.
Run Program
After programming, adjust the Fan and System switches, as desired. Press and release
start the program.
to
16
69-1385
Operating Your Thermostat
System switch must be set to Heat or Cool to perform the following:
TEMP
Temporarily Change Temperature for current period only — Press
; temporary indicator shows
Run Program
on display and cancels itself at the next scheduled change; to cancel sooner, press
.
TEMP
Hold Temp
Hold a Temperature Indefinitely (such as when on vacation) — Press
and
; HOLD
Run Program
appears on display; to cancel, press
.
Present Set
Check Current Temperature Setting — Press
.
Weekday
Weekend
Check Programs — Press
,
repeatedly to see each time and temperature; then press
Run Program
.
17
69-1385
Clear
Weekday
Weekend
Cancel Program — Press
,
until program to cancel shows; then press
.
Usage
Check Usage — Press
to see length of time heat or air conditioning has run today since
Clear
midnight; press again for yesterday’s usage, press again for cumulative; press
to clear
Run Program
cumulative reading, if desired; then press
.
Permanently Change a Program — Repeat Heating Program or Cooling Program steps, as
applicable.
Run Program
Return to Normal Program or Start Program — Press
.
18
69-1385
as a guide. The system on-time should be
optimized according to the type of system to
maximize comfort. Setting the screw “out one
turn” means turning the screw approximately
360° counterclockwise, or about one com-
plete turn.
Step 5. Adjust Fan Operation
Switch, As Required
❑ The thermostat fan operation switch, labeled
FUELSWITCH (see illustration) isfactory-set
in the F position. This is the correct setting for
most systems. If your system is an electric
heat system, set the switch to E to allow the
fan to turn on immediately with the heating in
a system when the G terminal is connected.
THERMOSTAT BACK
A
B
C
D
ADJUST SCREWS THROUGH HOLES
TO SELECT OPERATION DESIRED
DISPLAY °F C–IN
DISPLAY °C C–OUT
1 TURN
FUEL SWITCH
POSITION
HEATING SYSTEM
WARM AIR A–IN
FURNACE
HOT WATER A–OUT B–IN
BOILER 1 TURN
ELECTRIC A–IN
FURNACE
B–IN
F
F
E
B–OUT
1 TURN
Step 6. Adjust System On-Time,
°F/°C, As Required
W
Y
G
FOR HIGH EFFICIENCY FURNACE (90%+ AFUE)
ADJUST: SCREW A–OUT ONE TURN
SCREW B–IN
FUEL SWITCH – F POSITION
FUEL SWITCH
❑ The thermostat on-time is factory-set for a
warm air, gas or oil heating system. If you are
installing it on another type of system, adjust
the on-time accordingly by setting screws A
and B on the back of the thermostat. Use the
heating system table shown in the illustration
F
E
Rc
R
M8796A
19
69-1385
In the unlikely event that you want a longer
furnace on-time, readjust screws A and/or B as
follows:
IMPORTANT
When using a high efficiency furnace
such as a 90 percent or greater Aver-
age Fuel Utilization Efficiency (AFUE)
unit, adjust screw A out one turn and
leave screw B in.
First, turn both screws in completely, then
adjust for system type:
•
Warm Air Furnace—Set at the Hot Water
setting (A—out one turn, B—leave in).
Electric Furnace—Leave at the Warm Air
Furnace setting (A—leave in, B—leave in).
❑ The thermostat is set to read the temperature
in degrees Fahrenheit. If readings are
desired in degrees Celsius, adjust screw C
out one turn.
•
NOTE: This thermostat does not have a set-
ting for steam/gravity air; cycles would
not be long enough for accurate tem-
perature control.
20
69-1385
Step 7. Mount Thermostat
Mounting Plate
WALL ANCHORS (2)
WIRES THROUGH
WALL OPENING
❑ Position mounting plate on wall. Use level to
make sure mounting plate is level. Use a
pencil to mark the two mounting holes.
❑ Remove mounting plate from wall, and drill
3/16-inch holes in wall (if drywall) as marked.
For firmer material such as plaster or wood,
drill 7/32-inch holes. Gently tap anchors
(provided) into drilled holesuntil flush with the
wall.
WALL
MOUNTING
PLATE
❑ Reposition mounting plate over holes,
pulling wires through wiring opening.
❑ Loosely insert two mounting screws into
holes.
MOUNTING
SCREWS (2)
M1718
21
69-1385
❑ Level for appearance only; thermostat
functions properly even when not level.
❑ Tighten mounting screws.
LEVEL
M1714A
22
69-1385
Step 8. Wire Thermostat Terminals
NOTE: All wiring must comply with local codes
and ordinances. If unsure about house-
hold wiring procedures, call your local
heating/air conditioning contractor.
WIRE NUT SIZE FOR
TWO 18-GAUGE WIRES
METHOD TO INCREASE WIRE LENGTH
6 IN. (152 MM)
WIRE
FROM
WALL
❑ Refer to the labels you placed on the terminal
wireswhenyouremovedyour oldthermostat.
Match the letter of your old thermostat wire
with the terminal of the corresponding letter
on the back of your new thermostat. (See
wiring diagrams.) Hold the thermostat as
shown in illustration to minimize need for wire
extenders. If wires are still too short, use wire
connectors (purchased locally) to extend
wires. See illustration for guidelines on using
wire extenders.
OF 18-GAUGE
THERMOSTAT
WIRE. MATCH
INSULATION
COLORS
OR MARK
WIRE ENDS.
M1715A
❑ In 5-wire installations only, be sure to remove
the factory-installed jumper connecting termi-
nals R and Rc.
23
69-1385
❑ Loosen the terminal screws and slip each wire beneath its matching terminal. See illustrations for
wire insertion technique.
❑ Securely tighten terminals.
❑ Plug the hole in the wall with insulation to help prevent drafts from adversely affecting thermostat
operation.
JUMPER (FACTORY-
INSTALLED). REMOVE
IF 5-WIRE SYSTEM
INSERT
STRAIGHT
UNDER
5/16 in.
(8 mm)
STRIP
c
SCREW HEAD
R
R
END OF WIRE
VISIBLE HERE
M1712B
G
W
Y
M3002A
24
69-1385
2-WIRE HEAT-ONLY (JUMPER INTACT)
4-WIRE HEAT/COOL (JUMPER INTACT)
A
C
A
C
B
D
B
D
JUMPER
W
R
Y
G
W
R
Y
G
JUMPER
Rc
Rc
HEATING
RELAY OR
VALVE COIL
COOLING
CONTACTOR
COIL
HEATING
RELAY OR
VALVE COIL
L1
(HOT)
1
L2
FAN
L1
(HOT)
RELAY
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
M1709B
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
M1710B
25
69-1385
5-WIRE HEAT/COOL (JUMPER REMOVED)
3-WIRE COOL-ONLY (JUMPER INTACT)
A
C
A
C
B
D
B
D
W
R
Y
G
W
R
Y
G
JUMPER
Rc
Rc
HEATING
RELAY OR
VALVE COIL
FAN
RELAY
COOLING
CONTACTOR
COIL
COOLING
CONTACTOR
COIL
FAN
RELAY
1
1
L1
(HOT)
L1
L2
L1
(HOT)
L2
L2
1
(HOT)
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
M848A
M1711C
26
69-1385
Step 9. Mount Thermostat
NOTE: To remove thermostat from wall, first pull out at bottom of thermostat, then remove top.
SWING OPEN COVER TO
CHECK OPERATION.
A. ENGAGE TABS AT TOP OF
B. PRESS LOWER EDGE
OF CASE TO LATCH.
C.
THERMOSTAT AND SUBBASE.
AM
TU
LE
AV
E
Cl
oc
k/
Da
y
Ti
m
e
TE
M
P
Ru
n
Pr
ld
og
ra
m
W
ee
kd
ay
Ho
Te
m
p
W
ee
ke
nd
Cl
ea
r
Us
ag
e
Pr
es
en
t
S
et
Fan
uto
A
O
n
S
ys
te
m
C
ool
O
ff
H
eat
M13545
27
69-1385
Move the System switch to
Heat and the Fan switch to
Auto.
Cool
Off
Heat
Step 10. Check Thermostat
Operation After Programming
and Installing
M1703
Auto
On
M1705
TEMP
Heating
Press TEMP key until the set-
ting is about 10°F (6°C) above
room temperature. Heating
should start and the fan should
run after a short delay (immedi-
Do not check heating system operation by
jumpering thermostat terminals such as gas
valve, zone valve, and oil burner control at the
primary control. This damages the thermostat.
Instead, jumper R and W wires at the
thermostat.
ately if fan operation switch is set to E position).
Press TEMP key until setting is about 10°F (6°C)
below room temperature. The heating equip-
ment should shut off.
28
69-1385
Move the System switch to
Cool and the Fan switch to
Auto.
Cool
Off
Heat
Cooling
To avoid possible compressor damage, do not
operate the cooling system when outdoor
temperature is below 50°F (10°C). See
compressor manufacturer instructions.
M1704
Auto
On
M1705
TEMP
IMPORTANT
Press TEMP key until setting is
about 10°F (6°C) below room
temperature. The cooling
When cooling setting is changed, ther-
mostat delays up to five minutes
before turning on the air conditioner.
This delay protects the compressor.
equipment and fan should start.
Press TEMP key until the setting is about 10°F
(6°C) above room temperature. The cooling
equipment and fan should stop.
Move the System switch to Off;
Cool
Off
Heat
keep the Fan switch at Auto.
The system and fan should be
off.
M1707
Auto
On
29
69-1385
Step 11. Set Fan and System Switches
First set the Fan switch.
Then set the System switch.
Cool: The thermostat controls
your air conditioning
system.
Fan Auto: Normal setting for most
Auto
On
Cool
Cool
Cool
Off
Off
Off
Heat
Heat
Heat
homes. A single-speed fan will
turn on automatically with the air
conditioner or furnace. A two-speed fan
usually runs on high with the air conditioner
and on low with the furnace.
Off: Both the heating and air
conditioning systems are
off.
Fan On: The fan runs continuously.
Auto
On
Use for improved air circulation
during special occasions or for
more efficient electronic air
Heat: The thermostat
controls your heating
system.
cleaning. (In a heat-only system, fan runs
continuously only if fan relay is connected to
the thermostat.)
30
69-1385
Troubleshooting Guide
If...
Then...
Display does not come on. Set the System switch to Off. Remove batteries. Insert them backward
for at least five seconds to reset the thermostat. Replace batteries
correctly. Display should come on.
Make sure batteries are fresh and installed correctly.
Temperature display does You have reached the temperature setting limit. The setting range is
not go lower than 45°F
45°F to 88°F (7° to 31°C).
(7°C) or higher than 88°F
(31°C) during programming.
Temperature change occurs Check the program times for the questionable period. Be sure that AM
at wrong times.
and PM indications are correct. Make sure the current day and time
are correct. Reprogram, if necessary.
31
69-1385
If...
Heating does not come on. Check that the System switch is set to Heat.
Make sure the heating setpoint is above the room temperature.
Then...
Check the system fuse or circuit breaker and replace or reset, if
necessary.
Make sure the System switch is in the On position; set it to On if it is in
the Off position.
If temperature setting is higher than the current temperature and the
display says HEAT, contact Honeywell Consumer Services at 1-800-
468-1502.
Cooling does not come on. Check that the System switch is set to Cool.
Make sure the cooling setpoint is below the room temperature.
Check the system fuse or circuit breaker and replace or reset, if
necessary.
Make sure the System switch at the air conditioner is in the On
position; set it to On if it is in the Off position.
32
69-1385
If...
Then...
Cooling does not come on The thermostat has a built-in time delay on cooling. Allow five to ten
(Continued).
minutes after changing the setting before the air conditioner starts.
If temperature setting is lower than current temperature, and the
display says COOL, move the System switch from Cool to Off for ten
minutes. After ten minutes, return the switch to the Cool position. If air
conditioner comes on, compressor may have reached its high-limit
temperature protection and shut down.If air conditioner does not come
on after the ten minutes and the display says COOL, contact
Honeywell Consumer Services at 1-800-468-1502.
If two- or four-wire installation, verify R-Rc jumper is installed.
Press Present Set key to check the current temperature setting.
The house is too warm or
too cool.
If desired, change the temperature setting. See Cooling Program
section.
SYSTEM ON indicator is
lighted, but no heat is
Allow time for the furnace to heat up and the fan to come on before
checking for heat at the register. (Check to make sure system on-time
coming from the registers. is set correctly. See Step 6.)
33
69-1385
Toll-free Customer Assistance
For all questions concerning this thermostat, please read and follow the instructions. If additional
assistance is needed, call Honeywell Consumer Services at 1-800-468-1502, Monday - Friday,
7:00 a.m. - 5:30 p.m. Central time.
Before you call, please have the following information available—thermostat model number and
date code, type of heating/cooling system (hot water, warm air, oil, gas, etc.), and number of wires
connected to the thermostat.
NOTICE
This equipment is a Class B digital apparatus, which complies with Canadian Radio Interference
Regulations, CRC c.1374.
34
69-1385
Limited One-Year Warranty
Honeywell warrants this product, excluding battery, to be free from defects in the workmanship or materials, under normal use and
service, for a period of one (1) year from the date of purchase by the consumer. If, at any time during the warranty period, the
product is defective or malfunctions, Honeywell shall repair or replace it (at Honeywell’s option) within a reasonable period of time.
If the product is defective,
(i) return it, with a bill of sale or other dated proof of purchase, to the retailer from which you purchased it, or
(ii) package it carefully, along with proof of purchase (including date of purchase) and a short description of the malfunction, and
mail it, postage prepaid, to the following address:
Honeywell Inc.
Canada: Honeywell Limited/Honeywell Limitée
Product ServicesON15-FFE
Return Goods Department
1050 Berkshire Lane
Plymouth, MN 55441-4437
740 Ellesmere Road
Scarborough, Ontario M1P 2V9
This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by Honeywell that the
defect or malfunction was caused by damage which occurred while the product was in the possession of a consumer.
Honeywell’s sole responsibility shall be to repair or replace the product within the terms stated above. HONEYWELL SHALL NOT
BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES
RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY
OTHER FAILURE OF THIS PRODUCT. Some states do not allow the exclusion or limitation of incidental or consequential
damages, so this limitation may not apply to you.
35
69-1385
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY HONEYWELL MAKES ON THIS PRODUCT. THE DURATION OF
ANY IMPLIED WARRANTIES, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, IS HEREBY LIMITED TO THE ONE YEAR DURATION OF THIS WARRANTY. Some states do not allow limitations
on how long an implied warranty lasts, so the above limitation may not apply to you.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state.
If you have any questions concerning this warranty, please write our Customer Assistance Center, Honeywell Inc., P.O. Box 524,
Minneapolis, MN 55440-0524 or call 1-800-468-1502, Monday-Friday, 7:00 a.m. to 5:30 p.m., Central time. In Canada, write
Retail Products ON15-02H, Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 2C9.
36
69-1385
TYPICAL ENERGY SAVINGS FOR REPRESENTATIVE CITIES IN THE U.S. AND CANADA
Savings for Once-A-Day
10°F (5°C) decrease
Savings for Twice-A-Day
10°F (5°C) decrease*
Savings for 5°F (3°)
summer increase
30%
28%
26%
24%
22%
20%
18%
16%
14%
12%
10%
8%
6%
4%
2%
Calgary
Halifax
Vancouver Buffalo
Cleveland
Milwaukee
Denver
Des Moines Chicago
Boston
New York
Louisville
Portland
Wash., D C
San Dallas
Francisco Atlanta
Los Angeles San Diego
Minneapolis Edmonton
Cincinnati
Kansas City Philadelphia
St. Louis
St. Paul
Montreal
Ottawa
Toronto
Regina
Moncton
North Bay
Quebec
Omaha
Salt Lake
City
Detroit
Pittsburgh
Indianapolis
Seattle
Winnipeg
Columbus
St. John's
*Based on 10°F (5°C) decrease—(5°F [3°C] decrease
gives approximately 55 percent of these savings).
M2416A
37
69-1385
Home and Building Control
Honeywell Inc.
Honeywell Plaza
Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
P.O. Box 524
Minneapolis, MN 55408-0524
M2H 3N7
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
69-1385 G.H. 6-00
|