Hubbell Switch LXi 1300 User Manual

Hubbell Industrial Controls, Inc.  
Electric Fire Pump Controllers  
Specifications for LXi 1300 Controllers * Autotransformer Starting * July 2002  
The fire pump controller shall be factory assembled, wired, and tested as a unit assembly, shall conform to the requirements of the latest  
editions of NFPA-20 and NFPA-70, and shall be Listed/Approved by and bear the label of UL/FM. The controller shall be Hubbell-  
Lexington LXi 1300 equipped with LXi logic.  
The controller shall be of the combined manual/automatic type and be furnished in a floor mounted drip-proof steel Type 2 enclosure with  
lifting eyes. The enclosure shall be red with a non-glare surface. The controller shall be for auto-transformer starting and designed, tested,  
and marked for the rated horsepower and 3-phase voltage and frequency in a 40 degree C. ambient. Taps on the transformer shall allow  
voltages of 50, 65, or 80% to be applied for reduced current, closed-transition starting.  
All electrical components shall be accessible from the front for maintenance and service. No components or component wiring shall be  
permitted on the door of the enclosure. The controller shall have a common operating handle for both the line isolating switch and the  
controller circuit breaker mounted in the enclosure flange. The minimum withstand rating for the fire pump controller shall be 150,000  
amps RMS symmetrical at 200-600volts. The unit shall be Listed/ Approved with UL/FM as “Suitable For Use As Service Equipment”.  
The controller shall have separate and independent pressure settings with minimum run timing capable of a setting of 10 minutes. Settings  
of the pressures shall be established at the time of the field acceptance test. Provisions shall be included to allow manual or automatic  
shutdown in the field.  
The controller shall have two sets of Form “C” contacts for Pump Running, Phase Reversal, Power/Phase Failure, and one set of Form “C”  
contacts for Trouble. The Trouble contacts shall be activated by the following conditions: Invalid Configuration Memory, Emergency  
Manual Start, Pump Running, Phase Failure, Phase Reversal, Overload, Locked Rotor, Fail-to-Start, and Lockout.  
The controller shall be equipped with LXi intelligent fire pump control system logic. All firmware shall be non-volatile flash based CPLD  
(complex-programmable logic device). The boot-up time for the logic shall be 3 seconds or less. Controllers that do not boot-up and allow  
the pump to be started in 3 seconds or less are not acceptable. An RS232 serial port shall be supplied for downloading event history to a PC  
for analysis and printing.  
The digital pressure readings and settings shall be displayed on the LXi LCD mounted on the enclosure flange. The LCD screen shall be 4  
x 20 (4 lines of 20 characters) per screen, and the screens may be scrolled to give a total of 320 characters. The real time display shall give  
simultaneous 3-phase digital amps and volts for the pump power, and digital display for the system pressure. Controllers that do not  
simultaneously display digital 3-phase amps, line-to-line volt readings, and system pressure, are not acceptable.  
The event alarm caches shall be compartmentalized, and no compartment shall over-ride any other compartment. The compartments allow  
for analysis of four types of information events without having to look through all events including those not related to a problem. Events  
shall be shown with Date and Time for each event occurrence:  
1.  
2.  
3.  
4.  
Events that have occurred during a pump idle period  
Events that occurred during the last start period  
Events that occurred during the last run period  
Events that occurred during the last stop period.  
The LED displays shall be mounted on the enclosure flange and have an LED for the following, with provisions for five spare LED’s to be  
available and programmable for other options or event displays.  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Power Available  
Low Suction  
Pump Start Delay On  
Locked Rotor  
Pressure Switch Start  
Emergency Manual Start  
Fail to Start  
8.  
9.  
Phase Reversal  
Overload  
Local Manual Start  
Local Manual Stop  
Lockout On  
15.  
16.  
Remote Start  
Start Timer/Accelerate  
10.  
11.  
12.  
13.  
14.  
Run Timer On  
Pump Running  
The LED displays shall be mounted on the enclosure flange and have an LED for the following:  
Programming of the LXi logic shall be from the touch pad mounted on the enclosure flange. Programming shall be password protected so  
that only authorized personnel can change the logic functions. The fire pump controller shall be Model LXi 1300 equipped with LXi Logic  
as manufactured by Hubbell Industrial Controls, Inc.  
 

Hasselblad Camera Lens 0 5 User Manual
Honeywell Security Camera HD60 User Manual
Honeywell Weather Radio T775J User Manual
Hotpoint Clothes Dryer TCFG 87C User Manual
HP Hewlett Packard All in One Printer X476DN User Manual
Huawei Network Router HG523a User Manual
Hunter Fan Fan 21623 User Manual
Hunter Fan Fan 22793 User Manual
iHome MP3 Docking Station DF M12 User Manual
iLive DVD Player ID200B User Manual